Home › Guides › Home backup power

Home backup power: generators, batteries and safe connection

How to keep the fridge, boiler, lights and pumps running when the grid goes down, without endangering line workers. Covers portable and standby generators, home batteries and solar backup, changeover and transfer switches, interlocks, earthing and the neutral, and the rules in the UK, USA and Australia.

By Michael Johnson · Updated 16 November 2026 · How we check our guides

Read this first. Never plug a generator into a wall socket with a double-ended "suicide lead" or "backfeed cord". It sends generator voltage back through your meter into the street wiring. Line workers and neighbours have been killed this way, and it is illegal in the UK, the USA and Australia. Every method in this guide is designed to make that connection physically impossible.

1. Why backfeeding kills

When the grid goes down, the cables in your street are dead, and engineers work on them as dead cables. Your meter and the local transformer work in both directions. A 230 V or 120/240 V generator connected into a house circuit without isolation pushes power out through the meter, and the pole or substation transformer steps it back up to thousands of volts on the high-voltage side. A small portable generator can make a "dead" line lethal.

2. Your backup options compared

OptionWhat it powersSwitch-overProsCons
Portable generator + extension leadsIndividual appliances plugged straight into the generatorManualCheapest, no wiring work, legal everywhereLeads through windows or doors, no fixed loads (boiler, well pump, hard-wired lights)
Portable generator + inlet + changeover switch or interlockChosen circuits or the whole house within the generator's ratingManual, 1–5 minutesRuns hard-wired loads like boilers, furnaces and pumps; the best value for most homesNeeds an electrician; generator must be wheeled out and started
Automatic standby generatorWhole house or essential loadsAutomatic, 10–30 secondsHands-off; runs on mains gas, LPG or diesel for daysExpensive; needs a fixed site, fuel supply and maintenance contract
Home battery with backup gatewayEssential loads or whole houseAutomatic, usually under 1 second (some in milliseconds)Silent, no fumes, recharges from solar; also saves money every dayLimited energy (typically 5–15 kWh); not every battery system does backup
Portable power stationA few appliances plugged into itManual, or UPS-style pass-throughSilent, indoor-safe, no installationSmall capacity, 0.5–3 kWh typical
UPSRouter, computer, alarm panel, medical deviceInstantBridges short cuts with no interruptionMinutes to an hour or two only

See also the portable power station guide, the generator guide and the power outage plan.

3. What to keep running

Write a list of what you actually need in a cut, not everything in the house. Motors (fridges, freezers, pumps, air conditioners) draw a short surge of 2 to 7 times their running power when they start. That start-up surge, not the running total, usually decides the generator size.

LoadRunning power (typical)Start-up surge (typical)Notes
Fridge-freezer100–200 W600–1,200 WRuns about a third of the time; inverter-compressor models start softly
Chest freezer60–120 W400–800 WStays frozen for 1–2 days if kept shut
Gas boiler (UK, AU) or gas furnace blower (US)80–150 W boiler; 300–800 W furnace blowerUp to 2× runningMost need a proper neutral–earth reference to detect the flame (section 6)
Well pump, ¾–1 hp (common in rural US and AU)750–1,100 W2,500–4,500 WOften 240 V in the US; needs a 240 V generator output
Sump pump, ⅓–½ hp400–800 W1,300–2,200 WCritical in flood-prone basements
Router, fibre box, phone charging15–40 W–Run from a small UPS or power station
LED lighting5–10 W per lamp–
CPAP or oxygen concentrator30–100 W CPAP; 300–600 W concentrator–See the CPAP battery calculator
Microwave (800–1,000 W rated)1,200–1,500 W input–Rated power is output; input is higher
Kettle2,000–3,000 W (230 V), 1,500 W (120 V)–Use one big load at a time
Window or portable air conditioner500–1,500 W1,500–3,500 WInverter types start gently
Central air conditioning, 3 ton (US)3,000–4,000 WLocked-rotor current often 80–100 AUsually needs a soft-starter to run on a generator
Electric shower, oven, storage or resistance heating3,000–10,500 W–Normally left off on backup power

Add up your own list with the power consumption calculator. The surge figures above are typical; your appliance's rating plate or manual gives the real numbers.

4. Sizing a generator or battery

Generator: power

  1. Add the running watts of everything that may run together.
  2. Find the single largest start-up surge, and add the extra it draws above its running power (surge minus running).
  3. The generator's continuous rating must cover step 1, and its peak (surge) rating must cover step 1 plus step 2.
  4. Keep the continuous load to about 70–80% of the continuous rating. Generators run cooler, last longer and hold voltage better with headroom.

Example: fridge-freezer 150 W + chest freezer 100 W + gas boiler 120 W + router and lights 80 W + TV 100 W = 550 W running. Largest surge: fridge-freezer 1,200 W, which is 1,050 W above running. Peak needed ≈ 550 + 1,050 = 1,600 W. A 2.0–2.2 kW inverter generator covers this with room for a kettle used on its own.

Check your own numbers with the generator size calculator, then estimate fuel with the generator fuel consumption calculator.

Battery: energy

Voltage and phases

5. The three safe ways to connect

Connecting backup power safely: the three legal routes Every route makes it physically impossible for the generator or battery to feed the street wiring Street supply (utility / DNO) Meter + service fuse A. Manual changeover / transfer switch Changeover switch I – 0 – II (break-before-make) Consumer unit / main panel Generator inlet (BS EN 60309 / L14-30) Portable generator outdoors, well clear of openings B. Interlock kit on the main panel Main breaker ⟷ generator breaker sliding plate: only one breaker can be ON at a time US method; must be listed for that exact panel C. Battery / solar backup gateway Backup gateway / EPS opens a contactor when the grid fails (anti-islanding) Essential-loads sub-board fridge · boiler · lights Battery + hybrid inverter NEVER: a 'suicide lead' / 'backfeed cord' (plug to plug) into a wall socket Both pins of the male plug are live. It powers the street wiring through your meter and can kill a line worker or neighbour; it can also burn out the generator and start a fire when the grid comes back. It is illegal in all three countries and is the one connection method this guide does not describe. If you have no inlet, run appliances from the generator with heavy-duty outdoor extension leads instead. UK: BS 7671 Section 551.6 · USA: NEC 702.5 · Australia: AS/NZS 3000 and AS/NZS 3010
Route A is the standard in all three countries. Route B is a US method. Route C is for batteries and solar with backup. The red panel is the method none of them allow.

A. Manual changeover (transfer) switch with a generator inlet

B. Interlock kit (US)

C. Automatic transfer switch (ATS) and standby generators

Fitting the inlet and switch: who can do it

UKUSAAustralia
Who may fit itA competent electrician; in England and Wales usually notified under Building Regulations Part P. Work on the meter tails may need the network operator to remove the cut-out fuse.A licensed electrician, with a permit and inspection in almost every jurisdiction. Some states allow homeowners to do their own wiring with a permit.A licensed electrician only, who must give you a certificate of compliance (name varies by state). DIY electrical work is illegal.
Main ruleBS 7671 Section 551.6NEC Article 702AS/NZS 3000 Section 7.3 and AS/NZS 3010

6. Earthing and the neutral

This is the most misunderstood part of backup power, and it causes two common faults: RCDs or GFCIs tripping, and gas boilers or furnaces refusing to light.

7. Solar panels and home batteries in a power cut

8. United Kingdom rules

TopicRule or guidance
Wiring RegulationsBS 7671 (IET Wiring Regulations) Section 551 covers low-voltage generating sets. Regulation group 551.6 applies where a generator is a switched alternative to the mains: precautions must stop it running in parallel with the network, such as a three-position break-before-make changeover switch, mechanically or electrically interlocked switches, or a single transferable key system.
Prosumer installationsBS 7671 Chapter 82 (added in Amendment 2, 2022) covers installations with their own generation and storage, including "island mode" operation during a grid outage.
Generators running in parallelAny generator or battery inverter that can run connected to the grid (not just as a switched alternative) needs the network operator's acceptance under Engineering Recommendation G98 (up to 16 A per phase, notify after fitting) or G99 (larger, apply before fitting). Home batteries with backup fall under these.
Building RegulationsIn England, Part P: adding a new circuit or working on the consumer unit is notifiable, normally through a registered competent-person scheme electrician. Wales has similar rules; Scotland uses building warrants and BS 7671 through the technical handbooks; Northern Ireland has its own regulations.
Meter tailsFitting a whole-house changeover between meter and consumer unit means isolating the supply at the cut-out. Only the network operator, or someone they authorise, may remove the cut-out fuse or seal.
Battery locationPAS 63100:2024 sets out where home batteries may and may not go (not in bedrooms, escape routes, lofts or voids) and capacity limits of about 40 kWh indoors and 80 kWh outdoors.
Carbon monoxideNever run a generator indoors, in a garage or under a closed porch. Use a CO alarm to BS EN 50291 in the home. Since 2022, landlords in England must fit CO alarms in rooms with fixed combustion appliances (except gas cookers).
Fuel storagePetroleum (Consolidation) Regulations 2014: you can store up to 30 litres of petrol at home without telling the petroleum enforcement authority, in suitable containers (plastic up to 10 L each, metal up to 20 L each).

9. United States rules

TopicRule or guidance
National Electrical CodeArticle 702 (optional standby systems) applies to home backup generators. 702.5 requires transfer equipment that prevents inadvertent interconnection of the normal and standby sources. Interlocks must be listed for the panel. 702.4 covers capacity: a manual system must supply all loads intended to run at once; an automatic system must supply the full load or use load management.
Signs702.7: a permanent sign at the service equipment showing the type and location of the standby source; power inlets need a warning label too.
GeneratorsArticle 445: disconnecting means, overcurrent protection and, for one- and two-family dwellings, an emergency shutdown outside the house for permanently installed generators (445.19(C) in the 2023 NEC). GFCI on portable generator outlets (445.20). Grounding: 250.30 and 250.34.
Batteries and solarArticle 706 (energy storage systems), 705 (interconnected sources), 710 (stand-alone systems). Equipment listed to UL 9540 (ESS) and UL 1741 (inverters). Location limits in NFPA 855 and IRC R328: typically 20 kWh per unit, 40 kWh in utility rooms and basements, 80 kWh in garages and outdoors; never in sleeping rooms or closets opening into them. Check your state's adopted edition.
PermitsYour city or county building department enforces the NEC edition your state adopted (2017, 2020 or 2023, and some states already 2026). Transfer switches, inlets and standby generators need an electrical permit; gas lines need a plumbing or fuel-gas permit.
Utility rulesUtilities prohibit backfeeding in their tariffs and can disconnect service. Battery systems that connect in parallel need an interconnection agreement.
Carbon monoxideCPSC: run portable generators outside only, at least 20 feet (about 6 m) from the house, with the exhaust pointing away; about 100 people a year die from generator CO poisoning. Generators certified to ANSI/PGMA G300-2018 or UL 2201 have CO shut-off or low-emission features that sharply cut the risk. Most states require CO alarms in homes with fuel-burning appliances or attached garages.
EmissionsEPA small engine rules apply nationally. California's CARB rules phase out new gasoline small off-road engines, with portable generators affected from 2028; see the generator guide.
FuelLocal fire codes typically limit stored gasoline in a home or attached garage (often 25 US gallons in approved containers); use containers meeting ASTM F852 with child-resistant closures.
Tax creditsThe federal 25D residential clean energy credit for batteries and solar ended for systems placed in service after 2025. Some states and utilities still offer battery incentives.

10. Australia rules

TopicRule or guidance
Who can connectOnly a licensed electrician may connect a generator to house wiring, by fitting a changeover switch (and an inlet if needed) so the generator and network can never supply the house at the same time. They must give you a certificate of compliance. Severe penalties apply to non-compliant work.
StandardsAS/NZS 3000 (Wiring Rules) Section 7.3 covers alternative supplies and refers to AS/NZS 3010 (generating sets). AS/NZS 3010 also covers portable generators, their outlets and RCD or electrical-separation protection. Generator outlets should be standard 10/15 A AS/NZS 3112 type.
Portable usePlug appliances directly into the generator with heavy-duty extension leads rated at least as high as the generator, and protect plug joints from rain. Never connect to a power point or switchboard unless an electrician has fitted a dedicated inlet. Worksite generators must have RCD-protected outlets (AS/NZS 3012).
Product markingGenerators and leads sold in Australia should carry the RCM (Regulatory Compliance Mark).
Batteries and solarAS/NZS 4777.1 (installation of grid-connected inverters, including backup) and 4777.2 (inverter requirements); AS/NZS 5139 (battery installation and location: not in habitable rooms, ceiling spaces, wall cavities, under stairs or near exits). Network approval is needed before connection. The federal Cheaper Home Batteries Program (from July 2025) discounts eligible batteries.
Carbon monoxideNever run a generator indoors, in a garage or enclosed carport; keep exhaust away from doors, windows and vents.
FuelUse petrol containers marked AS/NZS 2906. State dangerous-goods laws limit how much fuel you can keep at home; check with your state regulator.

11. Fuel, runtime and storage

Generator typeTypical fuel useFuel for 24 hours
2 kW inverter, petrol, quarter to half load0.3–0.6 L/h (0.08–0.16 US gal/h)7–15 L
3.5 kW inverter, petrol, half load0.7–1.1 L/h17–26 L
7 kW open-frame, petrol, half load2–3 L/h (0.5–0.8 US gal/h)48–72 L
20 kW standby, natural gas, half load (US)about 5–6 m³/h (about 180–210 ft³/h)Piped supply

12. Carbon monoxide

DANGER A generator produces as much carbon monoxide as hundreds of idling cars. CO has no smell, and people have died with the garage door open or the generator just outside a window. Run it outdoors only, well away from doors, windows, vents and your neighbours' openings, with the exhaust pointing away.

13. Testing and maintenance

WhenTask
MonthlyStart the generator and run it under load for 20–30 minutes. Standby generators usually exercise themselves weekly; check that they do.
Every 3–6 monthsDo a full changeover: switch to generator, check that the boiler or furnace, pumps and fridge run, then switch back. Test RCDs or GFCIs on generator power.
Yearly, or by hoursOil and filter change, spark plug, air filter (often every 50–100 hours on portables). Check extension leads and the inlet for damage.
FuelRotate stored petrol every 3–6 months, or run it dry and store it empty; drain the carburettor for long storage.
Battery systemsCheck that backup mode is enabled, firmware is current and a reserve (often 20–30%) is held for outages. Test by switching off the main supply.

14. Approximate costs

Rough 2026 prices, including installation where relevant. Local labour rates vary widely.

ItemUKUSAAustralia
2–3.5 kW inverter generator£500–1,500$500–1,800A$800–2,500
Changeover switch and inlet, fitted£400–1,000$1,000–2,500 (transfer switch); $500–1,500 (interlock)A$800–2,000
Automatic standby generator, installed£6,000–15,000$8,000–20,000A$10,000–25,000
Home battery with backup, installed (about 10–13 kWh)£5,000–10,000 (0% VAT on batteries)$10,000–18,000A$8,000–16,000 before rebates

15. Frequently asked questions

Can I plug my generator into a wall socket if I switch off the main switch?

No. It is illegal in the UK, US and Australia. Someone can switch the main back on, the double-ended lead has live exposed pins, and the socket circuit isn't protected for that use. Fit an inlet and changeover switch, or use extension leads to individual appliances.

What size generator do I need to run a fridge and freezer in a power cut?

Usually 1,000–2,000 W. A fridge-freezer runs on 100–200 W but needs 600–1,200 W for a second when the compressor starts. A 2 kW inverter generator runs a fridge, a freezer, lights and phone charging comfortably.

Why won't my gas boiler or furnace work on generator power?

Most likely the generator's neutral isn't referenced to earth, so the flame-detection circuit can't see the flame. An electrician can confirm whether your changeover switches the neutral and arrange the correct neutral–earth bond.

Do solar panels work in a power cut?

Not on a normal grid-tied system: the inverter shuts down to protect line workers. You need a battery with a backup gateway or an EPS circuit, or a hybrid inverter designed for off-grid operation.

Is an interlock kit legal?

In the US, yes, if it is listed for your specific panel and installed under a permit; NEC 702.5 accepts it as transfer equipment. In the UK and Australia, use a changeover switch instead.

How far from the house should a generator be?

The US CPSC recommends at least 20 feet (about 6 m), with the exhaust pointing away from the house. UK and Australian authorities say outdoors and well away from doors, windows and vents. More distance is safer.

How long will a home battery run my house?

Divide usable capacity by your load. Essential loads of about 300 W average use 7 kWh a day, so a 13.5 kWh battery lasts about two days, longer if solar recharges it.

16. Sources

  1. IET, BS 7671 Wiring Regulations, Section 551 (generating sets) and Chapter 82 (prosumer installations): IET Wiring Matters
  2. BSI, PAS 63100:2024 battery storage in dwellings, summary: Marley
  3. UK Power Networks, power cuts and low carbon technologies: ukpowernetworks.co.uk
  4. UK legislation, Petroleum (Consolidation) Regulations 2014: legislation.gov.uk
  5. EC&M, NEC requirements for generators (Article 445, 2023 NEC): ecmweb.com
  6. EC&M, NEC requirements for optional standby systems (Article 702): ecmweb.com
  7. US CPSC, winter safety and portable generator CO deaths (January 2025): cpsc.gov
  8. UL Solutions, residential ESS separation and maximum quantities: ul.com
  9. Electrical Safety Office Queensland, permanently connected generators: electricalsafety.qld.gov.au
  10. Electrical Safety Office Queensland, portable generators: electricalsafety.qld.gov.au
  11. Government of South Australia, using generators for back-up power: sa.gov.au
  12. Energy Safe Victoria, generator safety fact sheet (2026): energysafe.vic.gov.au
  13. Standards Australia, AS/NZS 3010:2017 Electrical installations – Generating sets: standards.org.au

General guidance only. Electrical work on fixed wiring must be done by a qualified or licensed electrician in line with the rules where you live.