UPS runtime calculator

Enter your equipment's load and the UPS battery details to estimate how long it will keep running in a power cut.

Quick answer

A typical 1500 VA UPS (two 12 V 9 Ah batteries, about 216 Wh) runs 100 W for about 50 minutes, 200 W for about 20 minutes and 300 W for about 12 minutes. A small 600–700 VA UPS with one 7–9 Ah battery runs 100 W for about 15 minutes.

Load600–700 VA (1 × 12 V 7 Ah)1000 VA (1 × 12 V 9 Ah)1500 VA (2 × 12 V 9 Ah)
100 W≈ 15 min≈ 20 min≈ 49 min
200 W≈ 6 min≈ 9 min≈ 20 min
300 W≈ 4 min≈ 5 min≈ 12 min
500 W––≈ 6 min

Runtimes fall faster than the load rises because lead-acid batteries deliver less at high currents. Check your model's battery size.

Total power of everything plugged into the UPS. If you only know VA, choose VA.
V
Ah
%

Results

Estimated runtime—
Battery energy—
Battery current—

How it's calculated

Battery current = Load W ÷ Efficiency ÷ Battery bank voltage Runtime = 20 × (Ah ÷ (Current × 20)) ^ k × Usable fraction

UPS batteries are discharged quickly, often in 5–30 minutes, so Peukert's law is used to allow for the lower capacity lead-acid batteries give at high current. The batteries in most UPS units are wired in series, so their voltages add up.

Worked example

A home office UPS with two 12 V 9 Ah batteries (24 V) running a 300 W load at 85% efficiency draws about 14.7 A. That gives roughly 22 minutes, well short of the 37 minutes a simple Ah ÷ A calculation would suggest.

Typical UPS runtimes (600 VA to 1500 VA)

Estimated runtimes with new batteries, using the same method as the calculator above (sealed lead-acid, 85% inverter efficiency). A dash means the load is above that UPS's usual watt rating. Batteries vary between makes, so check your model's battery label and enter it above for a closer figure.

UPS (typical battery)50 W100 W200 W300 W500 W800 W
600 VA (1 × 12 V 7 Ah)58 min26 min12 min7 min——
850 VA (1 × 12 V 9 Ah)1 h 17 min35 min16 min10 min5 min—
1000 VA (2 × 12 V 7 Ah)2 h 8 min58 min26 min16 min9 min—
1500 VA (2 × 12 V 9 Ah)2 h 51 min1 h 17 min35 min22 min12 min7 min

Notice how the runtime falls faster than the load rises: doubling the load from 100 W to 200 W more than halves the runtime. That's the Peukert effect in lead-acid batteries.

Tips

Frequently asked questions

How long will a 1500VA UPS last?

It depends on the battery and the load, not just the VA rating. A typical 1500 VA UPS with two 12 V 9 Ah batteries runs about 1 h 17 min at 100 W, 22 minutes at 300 W and 12 minutes at 500 W when the batteries are new.

How long will a 1000VA UPS last?

A typical 1000 VA UPS with two 12 V 7 Ah batteries runs about 58 minutes at 100 W, 16 minutes at 300 W and 9 minutes at 500 W.

What's the difference between VA and watts?

VA is apparent power. Watts are real power. For computer equipment, watts are roughly 0.6–0.9 × VA. UPS units list both.