Fault finding off-grid and van electrics
A step-by-step method for finding faults with a multimeter, from the battery outwards: battery not charging, solar not producing, inverter cutting out, a battery going flat overnight, no power at all, hot connections and lithium BMS problems.
By Michael Johnson · Updated 17 November 2026 · How we check our guides
When an off-grid or van electrical system stops working, the cause is usually simple: a blown fuse, a loose connection, a wrong setting, a battery protecting itself. This guide gives a calm, step-by-step method to find the fault with a multimeter, covering "battery not charging", "inverter keeps cutting out", "solar not working", "battery dies overnight" and more, with quick checks you can do before calling anyone.
1. The method: from the battery outwards
- Look and smell: burnt smell, melted insulation, a tripped breaker, an error code on a display.
- Check the battery: its voltage at the terminals, and for lithium, the BMS status in the app.
- Check the main fuse and isolator.
- Work outwards along the path to the failed part, measuring voltage at each connection, until it disappears.
- Check settings: charger profiles, low-voltage cut-offs, app settings.
- Change one thing at a time and note what you've done.
2. Using a multimeter
- DC voltage (V⎓): measure across a battery, or between a point and battery negative. The most useful test.
- Voltage drop: measure between two ends of the same cable while current flows. More than a few tenths of a volt means a poor connection or thin cable.
- Continuity: only with power off. Checks fuses and cables.
- Current: a DC clamp meter measures current without breaking the circuit. Don't put a basic meter in series with big loads.
| 12 V battery at rest | Lead-acid (AGM/flooded) | LiFePO4 |
|---|---|---|
| Full | 12.7–12.9 V | 13.4–13.6 V |
| About half | 12.2–12.3 V | 13.1–13.2 V |
| Nearly empty | 11.8–11.9 V | 12.0–12.8 V |
Measure after the battery has rested for an hour with no charge or load. See the battery voltage chart; lithium's flat curve makes voltage a poor guide in the middle (see the battery monitoring guide).
3. Battery not charging
| Check | What you'll see | Fix |
|---|---|---|
| Charger output voltage at the battery terminals while charging | Should be 13.8–14.6 V (12 V system) | If lower at the battery than at the charger: voltage drop in cables or connections |
| Fuse between charger and battery | Blown, or a breaker tripped | Replace; find out why it blew |
| Charger settings | Wrong battery type or voltage | Set the correct profile |
| DC-DC charger trigger | No ignition/D+ signal, or smart alternator not detected | Check the trigger wire and settings |
| Lithium BMS | Charging blocked (too cold, too high voltage, cell imbalance) | Check the app; warm the battery; balance |
| Battery itself | Voltage rises fast and falls fast; old or sulphated lead-acid | Load test or capacity test; replace |
4. Solar not producing
- Check the sun: early morning, late afternoon, cloud and shade (even a small shadow on one cell) cut output hugely.
- Read the controller: PV voltage, PV current and battery voltage.
- PV voltage zero: check the panel isolator, MC4 connectors, string fuses and roof gland. Measure open-circuit voltage at the panel.
- PV voltage normal but no current: battery already full (normal), controller fault or wrong settings, or battery disconnected.
- PV voltage low: one panel in a series string is shaded or faulty, or a connector is damaged.
- Controller error: overvoltage in cold weather (too many panels in series), or over-temperature.
- Compare against expected yield with the solar panel output calculator; see the charge controller guide.
5. Inverter cuts out or won't start
| Symptom | Likely cause | Check / fix |
|---|---|---|
| Low-voltage alarm when a big load starts | Voltage drop in thin or long cables, loose lugs, weak battery | Measure voltage at the inverter terminals under load; thicker, shorter cables; tighten lugs |
| Overload when a motor starts | Start-up surge too big | Soft-starter or a bigger/low-frequency inverter |
| Inverter and lithium battery both go dead | BMS over-current trip | Check BMS current rating; add a battery in parallel |
| Over-temperature | Poor ventilation or a blocked fan | Clear space around it; clean the fan |
| RCD trips on the inverter | Earth leakage in an appliance or cable, or neutral–earth problems | Unplug appliances one at a time; see the earthing guide |
| Spark and click, then nothing, when connecting | Capacitor inrush tripping the BMS or fuse | Use a pre-charge resistor or switch |
6. Battery flat overnight or draining
- Turn everything off, then measure the standby current with a clamp meter on the main negative, or read it from the battery monitor.
- Normal standby loads: battery monitor, alarm, gas detector, router: typically 0.05–0.5 A. An inverter left on can draw 1–3 A at 12 V.
- Pull fuses one at a time until the drain disappears to find the circuit.
- Common culprits: inverter idle draw, a 3-way fridge left on 12 V, a stuck relay, a USB socket's LED, a diesel heater controller, a faulty cable chafing to chassis.
- Work out what your loads should use with the power consumption calculator.
7. No power at all
- Check the battery isolator and main fuse.
- Check the BMS: a lithium battery that went into low-voltage protection may need a charger connected (or a "wake" button) to restart.
- Check the negative connections, including any shunt and chassis link: a loose negative stops everything.
- Look for a tripped breaker or a battery low-voltage disconnect device.
8. Finding voltage drop and hot connections
- With a load running, measure across each connection (lug to terminal, fuse holder in to out). More than 0.1 V across a single connection means trouble.
- Feel (carefully) or use an infrared thermometer: a warm lug or fuse holder is a resistance, and resistance makes heat.
- Common causes: lugs not torqued, crimps done with pliers, corroded terminals, fuse holders under-rated for the current.
- Check with the DC voltage drop calculator what the cable alone should lose.
9. Lithium battery problems
- Won't charge in the cold: the BMS blocks charging below about 0 °C. Warm the battery or use a self-heating model.
- Cuts out at high state of charge: a high-voltage cell triggered the BMS; lower the charge voltage slightly and let it balance.
- Capacity seems low: the monitor hasn't been synchronised; charge to 100% to reset it.
- Shuts down under load: BMS current limit exceeded. See the lithium upgrade guide.
10. Frequently asked questions
Why is my leisure battery not charging?
Most often a blown fuse, a wrong charger setting, voltage drop from thin cables or a poor connection, a DC-DC charger not getting its ignition signal, or a lithium battery blocking charge because it's too cold.
Why does my battery go flat overnight?
A standby drain: an inverter left on, a fridge on 12 V, or a fault. Measure the current with everything off and pull fuses one at a time to find it.
Why does my inverter keep cutting out?
Usually voltage drop on the DC side during big loads, a battery or BMS that can't supply the current, or a motor's start-up surge.
Why is my solar panel not producing power?
Shade, a faulty connector or fuse, a battery that's already full, or a controller error. Check PV voltage and current at the controller.