12V wiring basics: cable, fuses, crimps and layout
Five rules that prevent most 12 V fires, choosing cable, the types of fuse and where they go, crimping lugs and terminals, bus bars and fuse boxes, colour codes, routing and protection, tools, and testing a system before you switch on.
By Michael Johnson · Updated 17 November 2026 · How we check our guides
Most 12 V fires and failures come down to the same handful of mistakes: undersized cable, missing or wrong fuses, poor crimps and loose connections. This guide is a practical reference for wiring a van, boat, shed or off-grid system safely: choosing cable, the types of fuse and where they go, crimping lugs properly, bus bars and distribution, colours, layout and testing.
1. Five rules that prevent most fires
- Every positive cable is protected by a fuse or breaker at its source end (as close as practical to the battery or bus bar).
- The fuse protects the cable: the fuse rating must not exceed what the cable can carry.
- Size cable for voltage drop as well as current: long 12 V runs need much thicker cable than the current alone suggests.
- Every connection is crimped properly, tight and protected from movement and moisture.
- Cables are supported, protected from chafing, and away from heat and sharp edges.
2. Choosing cable
- Use fine-stranded, flexible copper cable (automotive, marine "tinned" or welding cable). Solid-core house cable cracks with vibration.
- Insulation temperature rating matters: 105 °C cable (for example tri-rated, welding or marine cable) carries more current than 70 °C PVC, and is needed in engine bays.
- Tinned copper resists corrosion in boats and damp places.
- Check the real copper area: cheap "AWG" cable is sometimes copper-clad aluminium or undersized. Compare the stated mm² and strand count.
- Typical sizes at 12 V: 1.5–2.5 mm² for lights and USB; 4–6 mm² for a fridge or pump; 6–10 mm² for a solar controller output; 16–35 mm² for a DC-DC charger; 35–95 mm² for inverters.
Convert sizes with the AWG to mm² converter.
3. Fuses and breakers: types and where they go
| Type | Typical range | Use | Notes |
|---|---|---|---|
| Blade (ATO/ATC, mini, maxi) | 1–40 A (maxi to 120 A) | Branch circuits in a fuse box | Cheap and easy; low breaking capacity |
| MIDI / strip fuse | 30–200 A | Charger, DC-DC, small inverter feeds | Bolt-down; compact |
| ANL | 35–750 A | Inverter and battery main fuse (lead-acid) | Limited breaking capacity for lithium |
| MRBF (terminal fuse) | 30–300 A | Fitted directly on the battery terminal | High breaking capacity (about 10 kA at 14 V); great for lithium |
| Class T | 110–800 A | Main fuse on large lithium banks | 20 kA breaking capacity; fast-acting |
| DC circuit breakers | 5–300 A | Resettable protection, also used as an isolator | Must be DC-rated, with enough breaking capacity |
- Fit the main fuse within about 300 mm (12 in) of the battery; marine standards use 7 in (178 mm) for most connections.
- Fuse both ends of a cable that connects two power sources (for example a DC-DC charger or a battery-to-battery link).
- Size branch fuses at about 1.25 × the circuit's normal current, but never above the cable's rating.
- Lithium batteries can deliver thousands of amps into a short: the main fuse must have enough breaking capacity (Class T or MRBF).
4. Crimping lugs and terminals
- Use the right lug for the cable size and stud (for example 35 mm² with an M8 hole). Tinned copper tube lugs are best for heavy cable; avoid thin, stamped lugs.
- Strip exactly the length of the lug barrel, without nicking strands.
- Crimp with the correct tool: a ratchet crimper for small terminals, and a hydraulic or hex crimper for lugs above about 10 mm². Hammer crimpers give inconsistent results.
- Pull test every crimp: it shouldn't move.
- Seal with adhesive-lined heat shrink, which keeps out moisture and supports the cable.
- Don't solder heavy lugs as the only connection: solder wicks up the strands and they break where flexible meets stiff.
- Torque terminals to the maker's figure and recheck after a few weeks.
For photos and the full method, see crimping in the campervan wiring guide.
5. Bus bars, fuse boxes and switches
- Bus bars join many cables neatly. Use separate positive and negative bus bars rated for the total current, with covers.
- No more than four lugs per stud: use a bus bar instead.
- Fuse boxes (for example blade fuse boxes with a negative bus) feed branch circuits; feed the box with a cable and fuse sized for its total load.
- Battery isolator: a switch rated for the full current that disconnects everything (except perhaps bilge pumps or alarms on boats).
- Shunt: all negatives go through the battery monitor's shunt so it measures everything.
6. Colours and labelling
| Use | Common practice (vehicles, off-grid) | Boats (ABYC) | Mains AC (UK / US / AU) |
|---|---|---|---|
| DC positive | Red | Red | – |
| DC negative | Black | Yellow (or black) | – |
| AC live / line | – | Black or brown | Brown / black (red) / brown or red |
| AC neutral | – | White or blue | Blue / white / blue or black |
| Earth / ground | – | Green or green/yellow | Green/yellow / green / green/yellow |
Label both ends of every cable, and keep a wiring diagram with the system.
7. Layout, routing and protection
- Keep batteries, fuses, isolator and inverter close together with short, heavy cables.
- Run positive and negative cables together to reduce interference and voltage drop.
- Support cables every 300–450 mm, use grommets through metal, and use conduit or split loom where they could be damaged.
- Keep cables away from exhausts, heaters, fuel lines and moving parts.
- Keep AC and DC cables separate and clearly identified.
- Leave access to fuses, isolators and terminals for checks.
8. Tools worth having
- Ratchet crimper for insulated and non-insulated terminals
- Hydraulic or hex crimper for heavy lugs
- Cable cutters for heavy cable, and automatic wire strippers
- Heat gun (not a lighter) for heat shrink
- Multimeter, ideally with a DC clamp meter for current
- Torque wrench or screwdriver for terminals
9. Testing before you switch on
- With the battery disconnected, check each circuit for continuity and that positive isn't shorted to negative or chassis.
- Connect the battery with the main fuse removed, check voltages, then fit the fuse.
- Turn on circuits one at a time and check for heat, smell and correct operation.
- Run big loads (inverter, charger) at full power for 10–15 minutes and feel cables and lugs: anything more than warm needs attention.
- Measure voltage at the load under full current to confirm voltage drop.
10. Frequently asked questions
What size fuse should I use?
About 1.25 times the circuit's normal current, rounded up to the next standard size, and never larger than the cable's current rating. The fuse protects the cable.
Where should the fuse go?
At the battery or bus bar end of the positive cable, as close as practical (within about 300 mm). Fuse both ends if both ends can supply current.
Can I use solid-core cable in a van?
No. Vibration breaks solid cores. Use fine-stranded flexible cable, ideally tinned and rated for 105 °C.
Should I solder or crimp?
Crimp with the correct tool and seal with adhesive heat shrink. Solder alone creates a stiff point where strands break under vibration.
11. Sources
- Panbo, ABYC updated battery and electrical standards (2025): panbo.com
- Victron Energy, careful – alternator charging lithium: victronenergy.com
New to some of the terms? See the glossary. Not sure where to start? Try start here.