AWG to mm² converter

Choose a wire gauge to see its cross-sectional area in mm², diameter and resistance, plus the nearest metric cable size.

Quick answer

10 AWG = 5.26 mm², 12 AWG = 3.31 mm², 14 AWG = 2.08 mm², 8 AWG = 8.37 mm², 6 AWG = 13.3 mm², 4 AWG = 21.2 mm². When converting, round up to the next metric size: 10 AWG → 6 mm², 4 AWG → 25 mm².

Results

Area—
Diameter—
Resistance (copper, 20 °C)—
Nearest metric size up—
Guide current rating—

The formula

Diameter (mm) = 0.127 × 92 ^ ((36 − AWG) ÷ 39) Area (mm²) = π ÷ 4 × Diameter²

For gauges thicker than 1 AWG, use 0 for 1/0, −1 for 2/0, −2 for 3/0 and −3 for 4/0 in the formula.

Wire gauge chart

GaugeDiameter (mm)Diameter (in)Area (mm²)Ω per km (copper, 20 °C)Ω per 1,000 ft
4/0 AWG11.680.460107.220.1610.0490
3/0 AWG10.400.41085.030.2030.0618
2/0 AWG9.270.36567.430.2560.0779
1/0 AWG8.250.32553.480.3220.0983
1 AWG7.350.28942.410.4070.1239
2 AWG6.540.25833.630.5130.1562
3 AWG5.830.22926.670.6460.1970
4 AWG5.190.20421.150.8150.2484
6 AWG4.120.16213.301.2960.3950
8 AWG3.260.1288.372.0610.6281
10 AWG2.590.1025.263.2770.9988
12 AWG2.050.0813.315.2101.5881
14 AWG1.630.0642.088.2852.5252
16 AWG1.290.0511.3113.1734.0153
18 AWG1.020.0400.8220.9476.3845
20 AWG0.810.0320.5233.30610.1518
22 AWG0.640.0250.3352.95916.1419
24 AWG0.510.0200.2084.20825.6667

AWG vs metric cable

AWG sizes don't line up exactly with metric sizes. When converting, round up to the next metric size: 10 AWG (5.26 mm²) becomes 6 mm², 4 AWG (21.2 mm²) becomes 25 mm². Note that some cheap cable is labelled with a gauge number but has less copper than the standard, so check the actual mm² or strand count if you can.

mm² to AWG and diameter chart

Diameter is for a solid conductor of that area. Stranded cable is 10–20% larger across, and the insulation adds more, so measure the area or check the label rather than the outside diameter.

Metric sizeDiameter (solid conductor)Closest AWGAWG at least as thickΩ per km (copper, 20 °C)
0.5 mm²0.80 mm (0.031 in)20 AWG (0.52 mm²)20 AWG34.48
0.75 mm²0.98 mm (0.038 in)18 AWG (0.82 mm²)18 AWG22.99
1 mm²1.13 mm (0.044 in)17 AWG (1.04 mm²)16 AWG17.24
1.5 mm²1.38 mm (0.054 in)15 AWG (1.65 mm²)14 AWG11.49
2.5 mm²1.78 mm (0.070 in)13 AWG (2.62 mm²)12 AWG6.90
4 mm²2.26 mm (0.089 in)11 AWG (4.17 mm²)10 AWG4.31
6 mm²2.76 mm (0.109 in)9 AWG (6.63 mm²)8 AWG2.87
10 mm²3.57 mm (0.140 in)7 AWG (10.55 mm²)6 AWG1.72
16 mm²4.51 mm (0.178 in)5 AWG (16.77 mm²)4 AWG1.08
25 mm²5.64 mm (0.222 in)3 AWG (26.67 mm²)3 AWG0.69
35 mm²6.68 mm (0.263 in)2 AWG (33.63 mm²)1 AWG0.49
50 mm²7.98 mm (0.314 in)1/0 AWG (53.48 mm²)1/0 AWG0.34
70 mm²9.44 mm (0.372 in)2/0 AWG (67.43 mm²)3/0 AWG0.25
95 mm²11.00 mm (0.433 in)3/0 AWG (85.03 mm²)4/0 AWG0.18
120 mm²12.36 mm (0.487 in)4/0 AWG (107.22 mm²)larger than 4/0 (use kcmil)0.14
150 mm²13.82 mm (0.544 in)beyond 4/0 (about 296 kcmil)larger than 4/0 (use kcmil)0.11
185 mm²15.35 mm (0.604 in)beyond 4/0 (about 365 kcmil)larger than 4/0 (use kcmil)0.09
240 mm²17.48 mm (0.688 in)beyond 4/0 (about 474 kcmil)larger than 4/0 (use kcmil)0.07

US building wire ampacity (NEC Table 310.16)

For house wiring in the US, the National Electrical Code sets the current rating. Most terminals are rated 75 °C, so the 75 °C column is the one usually used. Small conductors are also limited by NEC 240.4(D): 14 AWG to a 15 A breaker, 12 AWG to 20 A and 10 AWG to 30 A.

Copper sizeAmpacity, 75 °C column
14 AWG20 A
12 AWG25 A
10 AWG35 A
8 AWG50 A
6 AWG65 A
4 AWG85 A
3 AWG100 A
2 AWG115 A
1 AWG130 A
1/0 AWG150 A
2/0 AWG175 A
3/0 AWG200 A
4/0 AWG230 A

These are for not more than three current-carrying copper conductors in a raceway or cable at 30 °C ambient. Derate for more conductors or hotter places.

UK and Australian cable ratings

Current ratings are guide figures for single-core copper cable. 'Standard PVC' uses conservative values for 70 °C insulation, bundled or enclosed; '105 °C' uses typical marine-table values for high-temperature cable run on its own. Always check the cable maker's rating, and derate for hot spaces such as engine bays.

Frequently asked questions

What is 10 AWG in mm²?

10 AWG is 5.26 mm². The nearest metric cable that's at least as thick is 6 mm².

What is 4 AWG in mm²?

4 AWG is 21.2 mm², so use 25 mm² metric cable as an equivalent.

Is 6mm² cable the same as 10 AWG?

Close. 6 mm² is slightly thicker than 10 AWG (5.26 mm²), so it can replace it.

What is 2.5mm² in AWG?

About 13 AWG. The nearest common US size at least as thick is 12 AWG (3.31 mm²); 14 AWG (2.08 mm²) is thinner.

What is the diameter of 4mm² cable?

The copper is about 2.26 mm across if solid. Stranded 4 mm² is a little larger, and the outside of the insulation larger still.

How many amps can 12 AWG carry?

In US house wiring, 12 AWG copper is limited to a 20 A breaker. In a short, well-ventilated 12 V run, 105 °C 12 AWG can carry a little more, but voltage drop usually limits it first.

Related calculators

Calculations and formulas last checked 8 November 2026. Spotted a problem? Tell us.