The formula
For gauges thicker than 1 AWG, use 0 for 1/0, −1 for 2/0, −2 for 3/0 and −3 for 4/0 in the formula.
Wire gauge chart
| Gauge | Diameter (mm) | Diameter (in) | Area (mm²) | Ω per km (copper, 20 °C) | Ω per 1,000 ft |
|---|---|---|---|---|---|
| 4/0 AWG | 11.68 | 0.460 | 107.22 | 0.161 | 0.0490 |
| 3/0 AWG | 10.40 | 0.410 | 85.03 | 0.203 | 0.0618 |
| 2/0 AWG | 9.27 | 0.365 | 67.43 | 0.256 | 0.0779 |
| 1/0 AWG | 8.25 | 0.325 | 53.48 | 0.322 | 0.0983 |
| 1 AWG | 7.35 | 0.289 | 42.41 | 0.407 | 0.1239 |
| 2 AWG | 6.54 | 0.258 | 33.63 | 0.513 | 0.1562 |
| 3 AWG | 5.83 | 0.229 | 26.67 | 0.646 | 0.1970 |
| 4 AWG | 5.19 | 0.204 | 21.15 | 0.815 | 0.2484 |
| 6 AWG | 4.12 | 0.162 | 13.30 | 1.296 | 0.3950 |
| 8 AWG | 3.26 | 0.128 | 8.37 | 2.061 | 0.6281 |
| 10 AWG | 2.59 | 0.102 | 5.26 | 3.277 | 0.9988 |
| 12 AWG | 2.05 | 0.081 | 3.31 | 5.210 | 1.5881 |
| 14 AWG | 1.63 | 0.064 | 2.08 | 8.285 | 2.5252 |
| 16 AWG | 1.29 | 0.051 | 1.31 | 13.173 | 4.0153 |
| 18 AWG | 1.02 | 0.040 | 0.82 | 20.947 | 6.3845 |
| 20 AWG | 0.81 | 0.032 | 0.52 | 33.306 | 10.1518 |
| 22 AWG | 0.64 | 0.025 | 0.33 | 52.959 | 16.1419 |
| 24 AWG | 0.51 | 0.020 | 0.20 | 84.208 | 25.6667 |
AWG vs metric cable
AWG sizes don't line up exactly with metric sizes. When converting, round up to the next metric size: 10 AWG (5.26 mm²) becomes 6 mm², 4 AWG (21.2 mm²) becomes 25 mm². Note that some cheap cable is labelled with a gauge number but has less copper than the standard, so check the actual mm² or strand count if you can.
mm² to AWG and diameter chart
Diameter is for a solid conductor of that area. Stranded cable is 10–20% larger across, and the insulation adds more, so measure the area or check the label rather than the outside diameter.
| Metric size | Diameter (solid conductor) | Closest AWG | AWG at least as thick | Ω per km (copper, 20 °C) |
|---|---|---|---|---|
| 0.5 mm² | 0.80 mm (0.031 in) | 20 AWG (0.52 mm²) | 20 AWG | 34.48 |
| 0.75 mm² | 0.98 mm (0.038 in) | 18 AWG (0.82 mm²) | 18 AWG | 22.99 |
| 1 mm² | 1.13 mm (0.044 in) | 17 AWG (1.04 mm²) | 16 AWG | 17.24 |
| 1.5 mm² | 1.38 mm (0.054 in) | 15 AWG (1.65 mm²) | 14 AWG | 11.49 |
| 2.5 mm² | 1.78 mm (0.070 in) | 13 AWG (2.62 mm²) | 12 AWG | 6.90 |
| 4 mm² | 2.26 mm (0.089 in) | 11 AWG (4.17 mm²) | 10 AWG | 4.31 |
| 6 mm² | 2.76 mm (0.109 in) | 9 AWG (6.63 mm²) | 8 AWG | 2.87 |
| 10 mm² | 3.57 mm (0.140 in) | 7 AWG (10.55 mm²) | 6 AWG | 1.72 |
| 16 mm² | 4.51 mm (0.178 in) | 5 AWG (16.77 mm²) | 4 AWG | 1.08 |
| 25 mm² | 5.64 mm (0.222 in) | 3 AWG (26.67 mm²) | 3 AWG | 0.69 |
| 35 mm² | 6.68 mm (0.263 in) | 2 AWG (33.63 mm²) | 1 AWG | 0.49 |
| 50 mm² | 7.98 mm (0.314 in) | 1/0 AWG (53.48 mm²) | 1/0 AWG | 0.34 |
| 70 mm² | 9.44 mm (0.372 in) | 2/0 AWG (67.43 mm²) | 3/0 AWG | 0.25 |
| 95 mm² | 11.00 mm (0.433 in) | 3/0 AWG (85.03 mm²) | 4/0 AWG | 0.18 |
| 120 mm² | 12.36 mm (0.487 in) | 4/0 AWG (107.22 mm²) | larger than 4/0 (use kcmil) | 0.14 |
| 150 mm² | 13.82 mm (0.544 in) | beyond 4/0 (about 296 kcmil) | larger than 4/0 (use kcmil) | 0.11 |
| 185 mm² | 15.35 mm (0.604 in) | beyond 4/0 (about 365 kcmil) | larger than 4/0 (use kcmil) | 0.09 |
| 240 mm² | 17.48 mm (0.688 in) | beyond 4/0 (about 474 kcmil) | larger than 4/0 (use kcmil) | 0.07 |
US building wire ampacity (NEC Table 310.16)
For house wiring in the US, the National Electrical Code sets the current rating. Most terminals are rated 75 °C, so the 75 °C column is the one usually used. Small conductors are also limited by NEC 240.4(D): 14 AWG to a 15 A breaker, 12 AWG to 20 A and 10 AWG to 30 A.
| Copper size | Ampacity, 75 °C column |
|---|---|
| 14 AWG | 20 A |
| 12 AWG | 25 A |
| 10 AWG | 35 A |
| 8 AWG | 50 A |
| 6 AWG | 65 A |
| 4 AWG | 85 A |
| 3 AWG | 100 A |
| 2 AWG | 115 A |
| 1 AWG | 130 A |
| 1/0 AWG | 150 A |
| 2/0 AWG | 175 A |
| 3/0 AWG | 200 A |
| 4/0 AWG | 230 A |
These are for not more than three current-carrying copper conductors in a raceway or cable at 30 °C ambient. Derate for more conductors or hotter places.
UK and Australian cable ratings
- UK: BS 7671 Appendix 4 gives ratings by installation method. As a rough guide, 2.5 mm² twin and earth clipped direct is rated about 27 A, 4 mm² about 37 A, 6 mm² about 47 A and 10 mm² about 64 A. A 2.5 mm² ring final circuit is protected at 32 A.
- Australia and New Zealand: AS/NZS 3008.1.1 gives the ratings; mains wiring must be done by a licensed electrician.
- 12 V and boats: use the DC cable size calculator, which checks both current and voltage drop.
Current ratings are guide figures for single-core copper cable. 'Standard PVC' uses conservative values for 70 °C insulation, bundled or enclosed; '105 °C' uses typical marine-table values for high-temperature cable run on its own. Always check the cable maker's rating, and derate for hot spaces such as engine bays.
Frequently asked questions
What is 10 AWG in mm²?
10 AWG is 5.26 mm². The nearest metric cable that's at least as thick is 6 mm².
What is 4 AWG in mm²?
4 AWG is 21.2 mm², so use 25 mm² metric cable as an equivalent.
Is 6mm² cable the same as 10 AWG?
Close. 6 mm² is slightly thicker than 10 AWG (5.26 mm²), so it can replace it.
What is 2.5mm² in AWG?
About 13 AWG. The nearest common US size at least as thick is 12 AWG (3.31 mm²); 14 AWG (2.08 mm²) is thinner.
What is the diameter of 4mm² cable?
The copper is about 2.26 mm across if solid. Stranded 4 mm² is a little larger, and the outside of the insulation larger still.
How many amps can 12 AWG carry?
In US house wiring, 12 AWG copper is limited to a 20 A breaker. In a short, well-ventilated 12 V run, 105 °C 12 AWG can carry a little more, but voltage drop usually limits it first.