Home › Heating, gas & water

Hot water cylinder and cold water tank size calculator

Enter how many people live there and how they use hot water at the busiest time of day. The calculator sizes the stored hot water, the reheat time and the cold tank.

Showers taken back to back in the morning rush.
Mixer showers 8–12 L/min; power showers 12–15 L/min; US low-flow heads 1.8–2.5 gpm.
min
60 °C (140 °F) controls Legionella; heat pumps often store at 50–55 °C with a weekly 60 °C cycle.
kW
UK immersion 3 kW; US electric water heater 4.5 kW; gas or boiler coil 15–25 kW; heat pump 2–3 kW of heat into the cylinder.

Results

Hot water used in the busiest hour—
Suggested stored volume—
Typical daily hot water—
Time to reheat the full cylinder—
Cold water storage tank (UK gravity systems)—

How the size is worked out

Hot fraction of a 40 °C shower = (40 − cold) ÷ (stored − cold) Busiest-hour hot water = showers × flow × minutes × hot fraction + baths Stored volume ≈ busiest-hour demand ÷ 0.8 (about 80% of a cylinder is usable before it runs cool) Reheat time (h) = litres × 4.186 × (stored − cold) ÷ 3,600 ÷ heater kW

The calculator also uses a floor of about 35 litres of stored water per person, a common UK rule of thumb, and rounds up to a common cylinder size.

Typical sizes

HouseholdUK cylinderUS tank water heaterAustralian storage tank
1–2 people, one shower120–150 L30–40 gal125–160 L
3–4 people, one bathroom170–210 L40–50 gal250 L
4–5 people, two bathrooms210–250 L50–60 gal315 L
5+ people, three bathrooms250–300 L+65–80 gal or a tankless unit400 L

Heat pump cylinders are sized larger, because they store water cooler and reheat slowly. Solar thermal cylinders are often 1.5–2 times normal size to store the day's heat.

Cold water storage tanks (UK)

US: first-hour rating

US water heaters are compared by their first-hour rating (FHR) on the label: how many gallons of hot water they deliver in an hour starting full. Choose an FHR at least equal to the "busiest hour" figure above, converted to gallons.

For the energy to heat water, see the water heating calculator. For tanks and rainwater, see the off-grid water guide.

Frequently asked questions

What size hot water cylinder do I need for 4 people?

Usually about 170–210 litres for one bathroom, or 210–250 litres with two bathrooms where showers run back to back.

How big should a cold water tank be?

In the UK, around 230 litres is common where the tank feeds the hot water cylinder. BS 6700 guidance suggests 200–300 litres for hot and cold, or about 100 litres per bedroom in larger homes.

How long does a hot water cylinder take to heat up?

A 200 litre cylinder heated from 10 °C to 60 °C by a 3 kW immersion takes about 3 hours 50 minutes. A gas boiler coil does it in under an hour.

What size water heater do I need for a family of four in the US?

Typically a 40–50 gallon tank with a first-hour rating of 60–70 gallons, or a tankless heater sized for two showers at once.

Related calculators

Calculations and formulas last checked 8 November 2026. Spotted a problem? Tell us.