Build a basic solar power kit: one panel, one battery, one inverter
A beginner's step-by-step guide to a small 12 V solar system: one 200 W panel (or a 37 V household panel), a 100 Ah lithium battery and a 600 W pure sine inverter. It concentrates on what makes a DIY system safe: fuses in the right place and properly crimped, tight connections.
By Michael Johnson · Updated 18 November 2026 · How we check our guides · Open the wiring diagram full size
1. What you'll build
| Part | Example | Why |
|---|---|---|
| Solar panel | 1 × 200 W "12 V" panel (Voc about 24 V, Isc about 10.5 A) | Low voltage, so the whole system stays at extra-low voltage. Easy to handle and mount. |
| Charge controller | MPPT, 100 V input, 20 A output (e.g. Victron SmartSolar 100/20) | Takes up to about 290 W of panel at 12 V, so there's room to add a second panel later. |
| Battery | 12.8 V 100 Ah LiFePO4 (1.28 kWh) with built-in BMS rated 100 A | Light, long life, safe chemistry. The BMS protects the cells, but it is not a substitute for a fuse. |
| Inverter | 600 W pure sine wave, 12 V, with built-in sockets (ideally with a built-in RCD/GFCI) | Runs normal mains appliances up to 600 W from its own sockets. It draws about 56 A from the battery at full power. |
| Protection | Battery fuse 100 A, inverter fuse 80 A, controller fuse 25 A, battery isolator switch, PV isolator | See Fuses. |
What it can run: the battery stores about 1.2 kWh of usable energy. That's a 60 W laptop for about 18 hours, or a 50 W TV and LED lights for an evening. On a good summer day in the UK, the panel puts back roughly 0.6–1 kWh. In midwinter, expect only a fraction of that. Sunnier parts of the USA and Australia do much better. Allow for the inverter's own standby draw: 5–10 W even with nothing plugged in, or about 0.2 kWh a day, so switch it off when not needed. A fridge compressor can briefly draw 3–5 times its running power when it starts, so check the inverter's surge rating. To plan your own use, try the off-grid solar system calculator.
Kettles, heaters, hair dryers, microwaves and power tools above 600 W won't run on this system. Trying will trip the inverter, or overload the battery BMS. To run them you need a bigger system with heavier cables and fuses. See our 3 kW and 5 kW off-grid solar guide.
Option B: one 37 V "household" panel
UK electrical wholesalers and DIY stores mostly sell the large 400–445 W panels made for house roofs, not "12 V" panels. A typical 405–435 W, 108-cell panel has a Voc of about 37 V, Isc about 13.5–14 A, and Vmp about 31 V. One of these works very well on this 12 V kit, and roughly doubles the solar power, but it needs a bigger charge controller:
| Item | Option A: 200 W "12 V" panel | Option B: about 410 W, 37 V panel |
|---|---|---|
| Panel voltage (Voc) | about 24 V (about 27 V on a frosty morning) | about 37 V (about 41 V at −10 °C). Still extra-low voltage, so DIY is fine. |
| Panel current (Isc) | about 10.5 A | about 13.8 A |
| Charge controller | MPPT 100 V / 20 A (e.g. Victron SmartSolar 100/20, 290 W at 12 V) | MPPT 100 V / 30 A, e.g. Victron SmartSolar MPPT 100/30: 100 V maximum PV voltage, 35 A maximum PV short-circuit current, 30 A charge, 440 W nominal at 12 V. Around £95 in the UK. Budget alternatives: EPEver Tracer 3210AN, Renogy Rover 30 A (both 100 V / 30 A). Check the datasheet for maximum PV voltage, maximum PV power at 12 V and maximum PV current. |
| Controller fuse F2 | 25 A | 40 A (30 A × 1.25; Victron recommends 35–40 A for the 100/30) |
| Controller cable C2 | 6 mm² (US 10 AWG) | 10 mm² (US 6 AWG): about 0.10 V drop over 1 m |
| Panel cable C1 | 6 mm² solar cable | 6 mm² solar cable: about 0.75 V (2.4%) over 10 m |
| PV isolator | 2-pole, ≥ 100 V DC, ≥ 16 A | 2-pole, ≥ 100 V DC, ≥ 20 A (1.25 × Isc = 17.3 A) |
| Size and weight | about 1.0 × 0.7 m, 10–12 kg | about 1.7 × 1.1 m, 20–22 kg. Needs a solid frame, and must be fixed to resist wind. |
| Energy on a good summer day (UK) | roughly 0.6–1 kWh | roughly 1.2–2 kWh, enough to fill the 100 Ah battery. Consider a second battery later. |
Use an MPPT controller, not a cheap PWM one, with a 37 V panel. A PWM controller connects the panel straight to the battery, dragging it down to about 13–14 V. You would lose more than half of the panel's power. An MPPT controller converts the panel's 31 V down to battery voltage and keeps nearly all of it.
Adding a second 37 V panel later: two in series is about 82 V Voc on a cold morning, so a 100 V controller still accepts it. But a 30 A controller at 12 V is capped at about 440 W, so for two panels plan a bigger controller (e.g. 100/50), or move to a 24 V battery.
Why the inverter must be pure sine wave: inductive loads
Mains electricity is a smooth sine wave. A pure sine wave inverter makes the same smooth wave, typically with under 3–5% distortion. A cheaper modified sine wave inverter makes a stepped, blocky wave with roughly 15–30% distortion. Resistive loads like heaters, kettles and old filament bulbs don't mind the difference. Inductive loads do.
What an inductive load is: anything with a coil of wire around iron, mainly motors and transformers. The coil resists sudden changes in current, so a stepped wave makes it work harder. On a modified sine inverter, inductive loads typically:
- run hotter: the extra harmonics cause extra losses in the iron and copper, which shortens motor and transformer life and wears insulation;
- hum, buzz or vibrate, and lose torque, so motors run slower or struggle to start;
- misbehave or stop working: speed controls, dimmers, timers and clocks can go wrong, and fittings with power-factor-correction capacitors can overload the inverter;
- cause radio interference, which matters if you run a radio shack or audio gear from the system.
Motors also need a big starting surge. A motor or compressor starting from rest can draw 3–7 times its running power for a fraction of a second up to a few seconds. Transformers draw a very large inrush for a few milliseconds when switched on. The inverter's surge rating, not just its continuous rating, has to cover this. Many 600 W pure sine inverters surge to about 1,000–1,200 W for a short time. Check the datasheet.
| Inductive load (examples) | Type | Typical running power | Typical start surge | On this 600 W kit? |
|---|---|---|---|---|
| Fridge, freezer, dehumidifier | Compressor (induction motor) | 60–150 W | 3–8× (often 600–1,000 W) | Usually yes, with a good-surge inverter. Test it. |
| Water pump, pond pump, booster pump | Induction motor | 50–750 W | 3–7× | Small pumps (under about 150 W) yes. Larger ones no. |
| Fans: desk, pedestal, extractor | Small induction motor | 20–60 W | 2–3× | Yes |
| Power tools: drill, jigsaw, grinder, circular saw | Universal (brushed) motor | 300–1,200 W | 2–3× briefly | A small drill yes. Grinders and saws usually no. |
| Air compressor | Induction or universal motor, starting under load | 750–1,500 W | 3–6× | No |
| Microwave oven | Transformer (high-voltage) and fan motor | Input 1,100–1,500 W for an 800 W oven | Inrush on switch-on | No |
| Washing machine, tumble dryer | Motor (plus a resistive heater) | 200–2,500 W | 2–4× (the motor) | No (the heater alone is too big) |
| Air conditioner, heat pump | Compressor | 500–2,000 W | 3–6× (less with "inverter" models or a soft-start) | No |
| Transformer-based equipment: older battery chargers, linear power supplies, toroidal audio amplifiers, ham radio linear PSUs, soldering stations | Iron-core transformer | 20–500 W | Very high inrush for a few ms | Small ones yes |
| Fluorescent tubes with magnetic ballasts, metal-halide (HID) lamps | Ballast (inductor) | 20–150 W | Modest | Yes on pure sine. HID lamps can be damaged on modified sine. |
| Hair clippers, shavers, sewing machines, mixers, CPAP machines | Small motors, some with electronic speed control | 10–150 W | Small | Yes on pure sine. They may run hot or erratically on modified sine. |
The figures are typical ranges to plan with. The real numbers are on each appliance's rating plate or in its manual, or you can measure them with a plug-in power meter or clamp meter. To size the inverter for continuous and surge watts, use the inverter size calculator.
Watts are not VA. Inductive loads have a power factor below 1, so they draw more current (VA) than their watts suggest. A 100 W fridge might draw 150 VA. Some inverters are rated in VA, and their continuous watt rating is lower. Leave about 25% headroom on top of the running watts.
Tips for starting motors: start one motor at a time. Switch on the biggest motor first, with nothing else running. Inverter "power saving" or search modes can fail to wake for small motor loads, so turn that mode off if a fan or fridge won't start. Soft-start kits for compressors (especially air conditioners and fridges) can cut the surge a lot.
2. Will it run my stuff? Real sun data, month by month
Solar output changes enormously through the year, especially in the UK. These figures come from PVGIS, the European Commission's free solar database (version 5.3). It uses 19 years of satellite and weather data, including shading from the local horizon.
Step 1: add up your daily use (worked example)
| Appliance | Power | Hours a day | Energy a day |
|---|---|---|---|
| LED lights, 4 × 5 W | 20 W | 5 | 100 Wh |
| Phone charging, 2 phones | – | – | 30 Wh |
| Laptop | 50 W | 3 | 150 Wh |
| Router or small radio | 10 W | 5 | 50 Wh |
| Inverter standby and losses | – | – | 70 Wh |
| Total for Option A (200 W panel) | 400 Wh/day | ||
| Add: 12 V or small mains fridge (averaged over the day) | – | – | 250 Wh |
| Add: TV, 50 W for 3 hours | 50 W | 3 | 150 Wh |
| Total for Option B (37 V, about 410 W panel) | 800 Wh/day | ||
To build your own list, use the power consumption calculator.
Step 2: what one kilowatt of panels makes each day, by month
Average kWh per day from 1 kWp of panels, tilted at about the latitude and facing the equator (south in the UK and USA, north in Australia), with 14% system losses. Multiply by your panel size: 0.2 for a 200 W panel, 0.41 for a 410 W panel.
| Location (tilt) | Jan | Feb | Mar | Apr | May | Jun | Jul | Aug | Sep | Oct | Nov | Dec | Year |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| London (50°) | 1.5 | 2.0 | 2.8 | 3.7 | 3.6 | 3.8 | 3.7 | 3.4 | 3.2 | 2.4 | 1.8 | 1.3 | 1014 |
| Glasgow (55°) | 0.9 | 1.6 | 2.4 | 3.3 | 3.4 | 3.3 | 3.3 | 2.9 | 2.5 | 1.8 | 1.3 | 0.8 | 841 |
| Seattle WA (45°) | 1.7 | 2.5 | 3.3 | 3.8 | 4.0 | 3.8 | 4.4 | 4.4 | 3.9 | 2.9 | 1.9 | 1.5 | 1160 |
| Phoenix AZ (35°) | 4.6 | 5.2 | 5.6 | 5.7 | 5.4 | 5.1 | 4.6 | 4.7 | 5.0 | 5.2 | 4.8 | 4.3 | 1829 |
| Sydney (35°) | 4.5 | 4.4 | 4.2 | 4.1 | 3.9 | 3.3 | 3.8 | 4.4 | 4.9 | 4.8 | 4.6 | 4.6 | 1559 |
| Melbourne (40°) | 4.8 | 4.8 | 4.3 | 3.6 | 2.8 | 2.5 | 2.8 | 3.3 | 4.1 | 4.5 | 4.5 | 4.7 | 1426 |
So a 200 W panel in London makes about 0.75 kWh a day in June but only about 0.27 kWh a day in December. That's a three-to-one difference. In Glasgow it's more than four-to-one.
Step 3: the whole system simulated, with the battery
PVGIS also simulates a complete off-grid system day by day: panel, battery and load. Each cell shows the average energy delivered per day (Wh) and, underneath, the percentage of days the battery ran flat. When it runs flat, the load is cut. These runs used a 1,280 Wh battery with 10% kept in reserve and PVGIS's standard evening-heavy load pattern.
Option A: 200 W panel, 400 Wh/day load
| Location | Jan | Feb | Mar | Apr | May | Jun | Jul | Aug | Sep | Oct | Nov | Dec | Year |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| London | 223 81% | 305 61% | 381 21% | 403 3% | 396 2% | 402 1% | 400 0% | 398 1% | 394 1% | 356 22% | 287 63% | 218 88% | 29% |
| Glasgow | 141 97% | 246 79% | 352 40% | 401 8% | 399 1% | 399 0% | 400 0% | 396 1% | 373 10% | 302 50% | 214 86% | 131 99% | 39% |
| Seattle WA | 265 60% | 353 32% | 394 5% | 404 1% | 398 0% | 402 0% | 400 0% | 399 0% | 396 0% | 378 9% | 295 45% | 234 71% | 19% |
| Phoenix AZ | 400 0% | 400 0% | 400 0% | 400 0% | 400 0% | 400 0% | 400 0% | 400 0% | 400 0% | 400 0% | 399 0% | 400 0% | 0% |
| Sydney | 398 0% | 400 0% | 398 0% | 400 0% | 398 0% | 397 1% | 400 1% | 403 0% | 402 0% | 400 0% | 398 0% | 402 0% | 0% |
| Melbourne | 400 0% | 398 0% | 400 0% | 396 0% | 393 0% | 386 11% | 403 4% | 407 0% | 402 0% | 401 0% | 401 0% | 399 0% | 1% |
Option B: about 410 W panel, 800 Wh/day load
| Location | Jan | Feb | Mar | Apr | May | Jun | Jul | Aug | Sep | Oct | Nov | Dec | Year |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| London | 447 82% | 580 66% | 711 35% | 785 8% | 783 7% | 793 4% | 799 1% | 789 4% | 773 12% | 686 40% | 565 68% | 443 87% | 34% |
| Glasgow | 289 97% | 482 81% | 654 51% | 770 18% | 787 8% | 791 5% | 797 4% | 780 9% | 721 31% | 581 61% | 433 86% | 269 99% | 46% |
| Seattle WA | 505 65% | 645 44% | 751 15% | 791 6% | 794 1% | 800 1% | 799 0% | 798 0% | 787 4% | 722 25% | 566 56% | 458 75% | 24% |
| Phoenix AZ | 798 1% | 799 1% | 800 0% | 800 0% | 800 0% | 800 0% | 800 0% | 800 0% | 799 0% | 800 0% | 799 0% | 797 2% | 0% |
| Sydney | 794 1% | 796 1% | 790 3% | 795 2% | 791 2% | 778 7% | 795 3% | 803 1% | 802 1% | 799 1% | 795 0% | 803 0% | 2% |
| Melbourne | 799 0% | 796 0% | 800 0% | 787 3% | 775 11% | 755 22% | 773 14% | 804 3% | 802 1% | 800 1% | 801 0% | 798 0% | 5% |
- UK: both options cover their load from April to September (except Glasgow, where Option B still runs flat on 18–31% of days in April and September). From November to January the battery runs flat on most days. Plan to use less in winter, top up from a mains charger or generator, or add panels.
- Seattle and similar northern US climates: similar to the UK, but slightly better.
- Arizona, Sydney and Melbourne: a single panel covers these loads almost all year. Melbourne's Option B runs flat on about 1 day in 5 in June (22%).
- Panels beat batteries in winter. A bigger battery doesn't help if the panel can't fill it. Adding panels (or a steeper tilt for winter) does.
Source: PVGIS 5.3 (European Commission JRC), PVcalc and off-grid (SHScalc) tools, queried 13 November 2026. UK locations use the PVGIS-SARAH3 database; US and Australian locations use PVGIS-ERA5. Treat results as long-term averages: a run of dull days can still flatten the battery in any month.
3. Choosing a battery
| LiFePO4 (lithium iron phosphate) | AGM / gel (sealed lead-acid) | Flooded lead-acid | |
|---|---|---|---|
| Usable energy from "100 Ah" | About 90–100 Ah | About 50 Ah (to keep it healthy) | About 50 Ah |
| Cycle life | 3,000–6,000+ cycles | 300–800 cycles | 500–1,200 cycles with maintenance |
| Weight (100 Ah) | About 11–13 kg | About 28–32 kg | About 25–30 kg |
| Cold weather | Must not charge below 0 °C without a heater or low-temperature cut-off | Charges in the cold (slowly) | Charges in the cold, but can freeze when flat |
| Ventilation | No gassing | Small amounts of gas if overcharged | Gives off hydrogen, so must be vented to outside |
| Best for | This guide's kit: almost always the best value over its life | Very occasional use, or very cold unheated sheds | Not recommended for beginners |
LiFePO4 buying checklist
- The BMS ratings match your system: continuous discharge of at least 100 A for this kit, a surge rating (for example 200 A for a few seconds) to start motors, and a charge rating of at least the controller's output.
- Low-temperature protection: the battery should stop charging below 0 °C. Better still, buy a self-heating model if it lives in an unheated shed.
- Safety certification listed by the seller and printed on the battery: cells or battery to IEC 62619 (or UL 1973 in the US), and UN 38.3 transport testing. If a seller can't tell you, buy elsewhere.
- Realistic weight and price. A genuine 12.8 V 100 Ah LiFePO4 weighs about 11–13 kg. A suspiciously light, very cheap "100 Ah" battery often has much less capacity. Test it: fully charge it, then run a known load and measure how many Ah or Wh you get out with a battery monitor.
- Warranty and support from a UK, US or Australian seller, and a BMS app or display so you can see cell voltages.
- Terminals: proper M8 bolt terminals, not push-on tabs, plus the maker's torque figure.
4. Can I do this myself?
The 12 V side of this kit (panel, controller, battery and inverter input) is all extra-low voltage: under 120 V DC. A DIYer can legally build that in all three countries. The rules change the moment you touch mains (230 V or 120 V) wiring.
| Country | OK to DIY | Needs a professional |
|---|---|---|
| UK | All the 12 V wiring. Plugging appliances into the inverter's own sockets. | Wiring the inverter output into a building's fixed circuits, a consumer unit or new sockets. That's a BS 7671 installation that must be inspected, tested and certified. In a dwelling it must also be notified under Building Regulations: Part P in England and Wales (through a registered electrician or building control), or a building warrant in Scotland. Never connect it to a house that also has a mains supply without a proper changeover switch fitted by an electrician. |
| Australia | Extra-low voltage work (up to 50 V AC / 120 V ripple-free DC), which covers the whole 12 V side and this single panel. Plugging appliances into the inverter's sockets. | Any 230 V fixed wiring must be done by a licensed electrician, by law, and certified. A fixed battery system of 1 kWh or more, like this one, comes under AS/NZS 5139 (in its lowest voltage class, DVC-A, up to 60 V DC). Follow its rules on location, barriers and labels. |
| USA | A portable or plug-in system like this is generally not "premises wiring". Plugging appliances into the inverter's sockets. | A permanently installed system, or anything wired into a building's panel, comes under the NEC (Articles 690, 706, 710) and usually needs a permit. Check with your local building department (AHJ). |
5. Wiring diagram
6. Fuses: the most important part
What a fuse is for
A fuse protects the cable, not the gadget. If a cable gets chafed through and touches the metal frame, or a tool drops across two terminals, the battery will try to push hundreds or thousands of amps through it. Without a fuse, the cable glows red, the insulation melts and burns, and nothing stops it until something gives way. A correctly sized fuse in the right place blows in a fraction of a second.
The four rules
- Every positive cable connected to the battery gets a fuse. That means the battery itself, the inverter, the charge controller and the DC fuse box. No exceptions. "It's only a short cable" isn't an exception.
- Put the fuse at the battery end of the cable. The battery is where the fault current comes from. A fuse at the far end leaves the whole cable unprotected. The main battery fuse F1 should be within 150 mm (6 in) of the battery's + terminal, or bolted straight onto it with a terminal fuse holder.
- Size it between the load and the cable. The fuse must be bigger than the normal current (×1.25 for headroom), but no bigger than the cable can carry. If in doubt, use a bigger cable, never a bigger fuse.
- Use a fuse that can actually break the fault. Every fuse has an interrupt rating (AIC): the largest current it can safely stop. A lithium battery can deliver more than 1,000 A. On the battery terminal, use an MRBF terminal fuse (10,000 A at 14 V) or a Class T fuse (20,000 A). A small blade fuse or a cheap "car audio" ANL fuse there may arc instead of breaking the circuit.
The fuses in this kit
| Fuse | Where | Rating | Type | Why that size |
|---|---|---|---|---|
| F1 | Battery + terminal, ≤150 mm | 100 A | MRBF terminal fuse or Class T | Matches the 100 A BMS. Protects the 25 mm² main cable. |
| F2 | Busbar, on the controller's positive cable | 25 A (Option B: 40 A) | MIDI or MEGA, interrupt rating checked (see below) | 20 A controller × 1.25, on 6 mm² cable. Option B: 30 A controller, 40 A fuse on 10 mm². Check the controller manual. |
| F3 | Busbar, on the inverter's positive cable | 80 A | MIDI or MEGA, interrupt rating checked (see below) | 600 W ÷ (12 V × 0.9) ≈ 56 A, × 1.25 = 70 A, so 80 A. 16 mm² cable. Check the inverter manual. |
| F4 | Busbar, on the DC fuse box feed (optional) | 30 A | MIDI or MEGA, interrupt rating checked (see below) | Feeds a small 12 V fuse box, which has its own blade fuse per circuit. |
| – | Solar panel | None needed | – | One panel can't push more than its own Isc (about 10.5 A, or 13.8 A for a 37 V panel) into its own cable. Fuses only become necessary with 3 or more panels in parallel. |
- Find the battery's prospective short-circuit current from its datasheet, or ask the maker. Some LiFePO4 BMSs limit it; many batteries can deliver several thousand amps for a moment.
- Check each fuse's interrupt rating at your voltage (at 14 V DC or more) on its datasheet. If it's at least the battery's short-circuit current, that fuse is fine on its own.
- If it isn't, use fuses that are (MRBF or Class T for the branch circuits as well, or a fuse system whose maker states a rating high enough), or use a main fuse and branch fuse combination the maker documents as tested.
Common fuse mistakes
- No fuse at all on the inverter cable, "because the inverter has its own protection". Internal protection doesn't protect the cable between the battery and the inverter.
- Fuse at the inverter end instead of the battery end.
- Fuse too big for the cable, for example a 150 A fuse on 10 mm² cable because "it kept blowing". If a fuse keeps blowing, find out why. Don't fit a bigger one.
- Fake or unbranded fuses. Very cheap ANL and "MIDI" fuses are often counterfeit and may not blow at their rating. Buy from known brands (Littelfuse, Blue Sea, Victron, Eaton/Bussmann) through reputable suppliers.
- Fuse holder too small or loose. The holder carries the full current. It needs studs that suit your lugs, and the nuts must be tight.
- No battery isolator. You need a way to disconnect the battery quickly in an emergency or to work on the system safely.
7. Good connections: crimps, lugs and terminals
How much heat a bad joint gives off with the inverter running flat out at 56 A (heat = current² × resistance):
| Joint | Extra resistance | Heat in the joint |
|---|---|---|
| Good hydraulic crimp, clean and torqued | well under 0.5 mΩ | under 1.5 W (barely warm) |
| Poor crimp | 1 mΩ | 3 W |
| Loose battery terminal nut | 5 mΩ | 16 W (too hot to touch) |
| Corroded or hammer-crimped lug | 10 mΩ | 31 W, as much as a soldering iron, concentrated in one spot |
Use the right tool for each cable
| Cable | Terminal | Right tool | Never use |
|---|---|---|---|
| Battery, inverter and busbar cables (16–25 mm²) | Tinned copper tube lug, matched to the cable size and the stud size (e.g. 25 mm² × M8) | Hydraulic crimper with the hex die marked for that cable size. If you don't want to buy one, many suppliers will make cables up to length for you. | Hammer crimpers, pliers, a vice, lugs made for a bigger cable |
| Controller and fuse box cables (4–6 mm²) | Tube lugs, or pre-insulated crimps (yellow 4–6 mm²) | Ratchet crimper with dies to match | Cheap stamped "plier" crimpers |
| Fine-strand cable in screw terminals (controller, inverter) | Bootlace ferrule | Ferrule ratchet crimper | Bare twisted strands, or ends tinned with solder |
| Solar panel cable | MC4 connectors, both halves the same make | MC4 crimp tool with the right die, plus MC4 spanners | Mixing MC4 brands; pliers |
Making a good crimp, step by step
- Cut the cable square with proper cable cutters.
- Strip exactly the depth of the lug barrel. Don't nick or cut any strands.
- Push the cable fully home. Copper should just show at the inspection hole, and the insulation should butt up to the barrel.
- Crimp with the die marked for that size. On long barrels, make two crimps.
- Inspect: an even hex shape, no cracks, no stray strands.
- Pull test: pull hard by hand. If the lug moves at all, cut it off and start again. Never re-crimp a bad one.
- Slide on adhesive-lined heat-shrink (red for positive, black for negative) and shrink it over the barrel and onto the insulation.
Bolting it up
- The lug sits flat against the terminal or busbar, with nothing in between. Never put a washer or nut under the lug. The one exception is an MRBF terminal fuse holder, which is designed to sit on the battery post: stack it exactly as its maker shows. Stack it as: terminal → lug → flat washer → spring washer (or nyloc) → nut.
- Tighten to the maker's torque figure with a torque wrench. Battery terminals are often only 4–10 Nm, and over-tightening strips them. Mark each nut with a dab of paint so you can see later if it has moved.
- No more than 3–4 lugs on one stud. Use a busbar instead of piling everything onto the battery post.
- Clean contact faces. Lithium battery terminals are often aluminium or copper: don't scrape them, and don't use dissimilar-metal hardware the maker hasn't approved.
- Never use crocodile clips, twisted-together wires, choc-block or terminal strip on battery cables, solid-core house wire, solder-only joints on battery cables, or cigarette-lighter plugs for anything over about 10 A.
8. Cable sizes
| Ref | Run | Max length (one way) | Current | Metric | US | Voltage drop |
|---|---|---|---|---|---|---|
| C1 | Panel → isolator → controller | 10 m | 10 A (B: 13 A) | 6 mm² solar cable (H1Z2Z2-K) | 10 AWG PV wire | ≈ 0.57 V (2.9% of 20 V). B: ≈ 0.75 V (2.4% of 31 V) |
| C2 | Controller → busbar (via F2) | 1 m | 20 A (B: 30 A) | 6 mm² (B: 10 mm²) | 10 AWG, the largest the 100/20 terminals take (B: 6 AWG) | ≈ 0.12 V (0.9%). B: ≈ 0.10 V |
| C3 | Battery → F1 → isolator → busbar | 0.5 m | up to 100 A | 25 mm² | 2 AWG | ≈ 0.07 V (0.5%) |
| C4 | Busbar → F3 → inverter | 1.5 m | 56 A | 16 mm² | 4 AWG | ≈ 0.18 V (1.4%) |
| – | Busbar → F4 → 12 V fuse box | 2 m | up to 30 A | 6 mm² | 8 AWG | ≈ 0.34 V at 30 A |
| – | All negatives | Same size as the matching positive cable, back to the negative busbar | ||||
Use fine-stranded copper cable rated for the job: tri-rated or welding cable for the 16–25 mm² runs, and solar cable for the panel. Keep the inverter cables as short as you can. The thick cables carry big currents at low voltage, so a few extra metres make a real difference.
9. Mounting the panel
Direction and tilt
| UK | USA | Australia | |
|---|---|---|---|
| Face | South (south-east to south-west loses only about 5–10%) | South | North |
| Tilt for all-year use | About 35–40° | About your latitude (25–45°) | About your latitude (20–40°) |
| Tilt for the best winter output (off-grid) | 50–60° | Latitude + 10–15° | Latitude + 10–15° |
For an off-grid system, winter output matters most, so tilt steeper than a grid-tied roof system would. A steep panel also sheds rain, snow and leaves better. The PVGIS figures in this guide use 50–55° in the UK and about the latitude elsewhere.
Shading
- Even a shadow across one corner can cut a panel's output by a third or more, because shaded cells hold back the whole string. Bypass diodes limit, but don't remove, the loss.
- Check the site at midday in midwinter, when the sun is lowest (about 15° above the horizon in London in December). Trees, fences and buildings that don't shade it in summer often do in winter.
Fixing it securely
- Wind is the main load. A 1.7 × 1.1 m panel catches the wind like a sail. Use proper aluminium mounting rails or a ground frame, with the panel maker's clamps at the clamping zones shown in its manual. Never drill the panel frame.
- Shed or garage roof: fix through to the rafters or purlins, not just the roof covering. Seal each fixing, and check the roof can take the weight (about 12 kg for a 200 W panel, 21 kg for a 410 W panel, plus rails).
- Ground frame: anchor it with ground screws, concrete pads or ballast, and keep the bottom edge high enough to clear grass and snow.
- Leave an air gap behind the panel (at least 50–100 mm) so it stays cool. Hot panels make less power.
Cabling outdoors
- Use solar cable (UV-resistant, double-insulated) for the whole outdoor run, and MC4 connectors from one brand, kept off the ground.
- Bring the cable into the building through a cable gland (IP68) or a sealed solar entry box, with a drip loop below the entry so water runs off rather than in.
- Clip cables to the rails with UV-stable stainless or black UV-rated ties. Clear plastic ties go brittle in a year. Don't let cables rest on sharp edges or hang loose to flap in the wind.
- The PV isolator mounted outside must be rated IP65 or better.
10. Step-by-step build
- Plan the layout on a board: battery at the bottom, isolator and busbars above, then controller and inverter. Keep it in a dry spot with air around the inverter and controller.
- Mount everything before connecting any cables. Strap or clamp the battery down so it can't move.
- Make up all the cables to length, crimped, pull-tested and heat-shrunk, as in the good connections section.
- Fit the negatives, except the battery's own negative. Connect the shunt (if used) to the negative busbar, then the controller and inverter negatives to the busbar. Leave the cable from the battery's − terminal disconnected, with its lug taped or covered, until step 7. While it's off, nothing in the system is connected to the battery.
- Fit the positives with all the fuses in place: F1 at the battery, the isolator (switched OFF), the busbar, then F2, F3 and F4 to each device. With the battery negative off, none of this is live yet.
- Check everything twice: red to +, black to −, every fuse the right rating, every nut torqued, the isolator OFF, the inverter's own switch OFF.
- Connect the battery negative last. Use insulated tools, and keep the spanner away from the + terminal. If the inverter manual asks for it, pre-charge its capacitors through a resistor first, to avoid a spark. Then switch the battery isolator ON. The controller should now show battery voltage.
- Only now connect the solar panel. Cover the panel (or keep its isolator OFF), plug in the MC4s, then switch on. Never connect the panel to the controller before the battery.
- Switch on the inverter with nothing plugged in. Check that its display or LEDs are normal.
- Plug in a small load (a lamp), then bigger ones, while watching for warnings.
- To change F2, F3 or F4: switch the battery isolator OFF and the solar PV isolator OFF, switch off and unplug any mains or generator charger, switch the inverter off and wait for its capacitors to discharge, then check with a meter that the busbar reads 0 V before touching it.
- To change F1 or work on the battery terminals: switch the isolator OFF, then disconnect the battery negative at the battery first and cover its lug. Work with insulated tools, and refit the negative last. If your battery has a BMS on/off switch, turn it off as well.
11. Settings
- Charge controller: choose the LiFePO4 profile, or enter the battery maker's charge (absorption) and float voltages. Don't use a lead-acid profile on a lithium battery. Typical LiFePO4 settings are absorption 14.2–14.4 V and float 13.5 V. Turn off equalisation and temperature compensation.
- Low temperature: most LiFePO4 batteries must not be charged below 0 °C. Use a battery with low-temperature protection or a self-heating battery, or keep the system somewhere frost-free.
- Inverter low-voltage cut-off: set it to the battery maker's recommendation (often 11.5–12 V for 12.8 V LiFePO4), so the inverter switches off before the BMS has to.
- Inverter earth and shock protection: connect the inverter's chassis or earth terminal exactly as its manual says. That is usually the DC negative busbar or system earth point, or an earth electrode for a fixed installation. The best choice is an inverter with a built-in RCD/GFCI on its sockets. A plug-in RCD between the inverter and your appliances only works if the inverter bonds its output neutral to earth, and many small inverters have a floating output. Check the manual, then plug the RCD in and press its test button: if it doesn't trip, it isn't protecting you.
12. Multimeter basics
A basic digital multimeter (about £20–40) and, ideally, a DC clamp meter are the two tools that make this system safe to check. Here's how to do each test the guide asks for.
| Test | Meter setting | How | What's good |
|---|---|---|---|
| Battery voltage | DC volts (V⎓), 20 V range or auto | Red probe on +, black on − | LiFePO4 at rest (no charge or load for an hour): 13.3–13.4 V is about 80–95%; 13.1–13.2 V about half; 12.8–12.9 V about 20%; below about 12.5 V nearly empty. The curve is very flat, so use a battery monitor for state of charge. |
| Polarity before fitting a fuse | DC volts | Red on the cable you think is +, black on − | A positive reading means correct. A minus sign means it's reversed: stop and fix it. |
| Panel open-circuit voltage (Voc) | DC volts, 200 V range | With the PV isolator OFF, measure at the panel side of the isolator | Close to the panel's Voc (about 22–24 V for Option A, 35–40 V for Option B). It's higher in cold sun and lower in heat. |
| Continuity of a cable | Continuity (beeper) or ohms, power OFF | Probe each end of the same cable | A beep, or under 1 Ω |
| No short between + and − busbars | Ohms, battery disconnected | One probe on each busbar | Not 0 Ω. The reading may climb as capacitors in the inverter charge, which is normal. |
| Volt drop across a joint | DC millivolts (mV), system running under heavy load | One probe on the cable just before the lug, the other on the terminal or busbar under it | At about 56 A: under 10–15 mV is good. Remake anything above about 30 mV. |
| Current | DC clamp meter (it must be DC-capable, Hall-effect type; many cheap clamp meters read AC only). Don't use the meter's 10 A socket. | Clamp around one cable only, positive or negative | Below the fuse rating, and roughly what you expect from the load |
Never measure battery current by putting the multimeter's probes across the battery or the fuse with the meter on its amps setting. That's a direct short through the meter, which can explode its internal fuse or the meter itself. Use a clamp meter, or read the battery monitor.
13. Test it properly
- Fuse check: every fuse fitted matches the table in the fuses section, and none is missing.
- Polarity: measure each connection with a multimeter before fitting its fuse.
- Volt-drop test under load: run something close to 600 W. With the meter on millivolts, measure across each joint, from the cable to the lug and from the lug to the terminal. At 56 A a good joint reads under about 10–15 mV. Remake any joint above about 30 mV, or one well above the others.
- Heat check: after 30–60 minutes at full load, carefully feel each lug and fuse holder (or use an infrared thermometer). Cables and joints should be barely warm. A lug warmer than the cable either side of it is a bad joint.
- Re-check torque after a week, then every few months. Copper settles and connections loosen with temperature changes.
14. Where to put it, and what never to do
- Choose a dry, frost-free place where the system won't get hot: a garage, shed, workshop or utility room. Never in a bedroom, an escape route, a loft space or near flammable stores. Leave air gaps around the inverter and controller.
- Keep a CO₂ or dry-powder fire extinguisher nearby, fit a smoke alarm in the room, and keep children and pets away from the battery terminals.
- Cover the battery terminals. Use insulated spanners, and take off rings and watches before working on the battery.
- Never back-feed a building by plugging the inverter into a wall socket with a male-to-male lead (a "suicide lead"). It can kill you or a utility worker, and it's illegal.
- Don't connect the panel straight to the battery without a controller. Don't run a lithium battery without a BMS. Don't mix battery types or ages in parallel.
15. Troubleshooting chart
| Symptom | Likely causes | What to check or do |
|---|---|---|
| Controller shows no solar input | PV isolator off. MC4 not fully clicked. Reversed polarity. Night or deep shade. A blown fuse if string fuses are fitted. | Measure Voc at the isolator (meter section). Check MC4s and polarity. Check for shade at that time of day. |
| Solar input present, but little or no charging | Battery already full. Charge voltages set too low. BMS has stopped charging (cold or high cell). Controller fuse F2 blown. Thin or long cables. | Check the controller's state (float / absorption / off) and the battery temperature. Check the F2 fuse and the controller's battery voltage reading against the meter. |
| Inverter beeps or shuts down when a load starts | Start surge too high for the inverter. Low battery voltage. Cables too thin or too long, so the voltage sags. A bad joint. | Measure the battery voltage at the inverter terminals while the load starts. A large drop compared with at the battery means cable or joint trouble. Check the surge rating against the inductive-load table. |
| Inverter runs light loads but trips on heavy ones | The BMS's current limit or surge limit is being reached. A loose joint heating up. | Check the BMS app for over-current events. Do the millivolt test on every joint under load. |
| Battery suddenly reads 0 V, or everything goes dead | The BMS has shut off (low voltage, over-current, temperature). The main fuse F1 has blown. | Check F1. With all loads off, charge or "wake" the battery as its manual describes. Find out why before switching back on. |
| A fuse keeps blowing | A real overload, a short or chafed cable, or an inrush current. | Never fit a bigger fuse. Disconnect the loads and check the cable for damage. Measure the actual current with a clamp meter. |
| A lug, fuse holder or terminal is warm | A loose nut, a poor crimp, corrosion, or a lug the wrong size for the cable or stud. | Switch off, then remake the joint (new lug if crimped badly), clean it, and torque it correctly. Re-test with the millivolt test. |
| Battery doesn't last as long as it used to | Lost capacity. The BMS is balancing a weak cell. Daily use has crept up. Winter. | Compare a full-to-empty test with the rated capacity. Check the BMS cell voltages (a big spread means imbalance). Compare your use with the sun data tables. |
| Radio or TV interference | Inverter or controller noise, or long unscreened DC cables. | Keep positive and negative cables together. Fit ferrite cores on the DC and AC leads. Earth the inverter case as its manual says. Pure sine inverters are much quieter than modified sine. |
16. Maintenance schedule
| When | Check |
|---|---|
| First week | Re-torque every bolted joint (copper and lugs settle). Do the heat check at full load again. |
| Monthly | Look over the cables and the panel for damage, chafing or animals chewing. Read the battery monitor or BMS app: cell voltages, cycles and temperature. Check the controller's history for low-charge days. |
| Every 3 months | Clean the panel with plain water and a soft brush (no detergent, no pressure washer). Check the MC4s are dry and fully latched. Check the fuse holders and terminal covers. |
| Yearly | Torque check of every joint and the millivolt test under load. Capacity test of the battery. Update controller and inverter firmware. Check the panel fixings and frame after the winter storms. Test any RCD with its button. |
| Before winter | Steepen the panel tilt if it's adjustable. Make sure the battery is somewhere above 0 °C, or that its low-temperature cut-off works. Plan a backup charge source. |
17. Upgrade path
- A second battery: use an identical model, ideally bought at the same time. Each battery gets its own fuse on its positive. Fit a main fuse after the point where they join, as in our 3 kW / 5 kW guide, because two fuses in parallel add up. Use equal cable lengths to the busbar so they share the load evenly.
- A second panel: with Option A, a second 200 W panel in parallel gives about 21 A Isc, which needs a 30 A controller. With Option B, a second 37 V panel in series (about 82 V cold) fits a 100 V controller, but a 30 A controller at 12 V is capped at about 440 W, so move up to 100/50, and upsize F2 and the controller cable to suit (for example 60 A and 16 mm²).
- More than about 800–1,000 W of panels or inverter: move to 24 V. At 12 V, a 2,000 W inverter draws about 185 A, which needs 50–70 mm² cable and a 250 A fuse. At 24 V the current halves. Changing voltage means a new battery (or two in series, with a balancer), a new inverter, and reprogramming the controller.
- Bigger than that: see our 3 kW and 5 kW off-grid solar guide, where the mains side becomes a full electrical installation.
18. Approximate costs
These are typical retail price ranges at November 2026, rounded, for budget planning only. Prices vary a lot, so check current prices.
| Item | UK (£) | USA ($) | Australia (A$) |
|---|---|---|---|
| Panel: Option A 200 W / Option B about 410 W | 90–180 / 90–160 | 120–220 / 120–220 | 150–300 / 150–300 |
| MPPT controller: 100/20 / 100/30 | 70–110 / 95–140 | 90–140 / 120–170 | 140–220 / 180–260 |
| LiFePO4 battery, 12.8 V 100 Ah | 200–450 | 200–500 | 350–800 |
| Inverter, 600 W pure sine | 80–250 | 90–300 | 150–450 |
| Fuses, holders, isolators and busbars | 80–160 | 100–200 | 150–300 |
| Cable, lugs, heat-shrink, glands | 60–120 | 70–150 | 100–220 |
| Tools: hydraulic crimper, ratchet crimpers, MC4 tool, multimeter, torque wrench | 80–200 | 100–250 | 150–350 |
| Mounting rails or frame | 40–150 | 50–200 | 80–300 |
| Typical total | about 700–1,650 | about 850–1,900 | about 1,300–3,000 |
19. Printable checklists and labels
Before you switch on
- ☐ Every positive cable has a fuse at the battery end: F1 100 A, F2 25/40 A, F3 80 A, F4 30 A.
- ☐ F1 is within 150 mm of the battery + terminal, or mounted on it.
- ☐ Every fuse rating is at or below its cable's rating.
- ☐ Every fuse's interrupt rating is at least the battery's short-circuit current (or a documented tested combination).
- ☐ Every crimp was made with the correct tool and die, inspected and pull-tested.
- ☐ Every lug sits flat with nothing under it, is torqued to spec and paint-marked.
- ☐ Polarity is checked with a meter on every cable before its fuse goes in.
- ☐ No short between the + and − busbars (battery disconnected).
- ☐ The battery is clamped down, its terminals covered, and it's in a frost-free, ventilated, non-sleeping area.
- ☐ The controller is set to the LiFePO4 profile or the maker's voltages.
- ☐ The battery is connected to the controller before the panel.
- ☐ The inverter output is used only through its own sockets, with no connection to building wiring.
- ☐ A smoke alarm and a CO₂ or powder extinguisher are nearby.
Fuse schedule card (stick inside the enclosure lid)
| Fuse | Circuit | Rating | Type | Cable |
|---|---|---|---|---|
| F1 | Battery main | 100 A | MRBF / Class T | 25 mm² |
| F2 | Solar controller | 25 A (B: 40 A) | MIDI / MEGA | 6 mm² (B: 10 mm²) |
| F3 | Inverter | 80 A | MIDI / MEGA | 16 mm² |
| F4 | 12 V fuse box | 30 A | MIDI / MEGA | 6 mm² |
Suggested labels
Battery feed only: also open the PV isolator and check the busbar reads 0 V before working on F2–F4. F1 stays live: disconnect the battery negative first.
Open the PV isolator before disconnecting
High short-circuit current. Insulated tools only.
Plug-in use only – not connected to building wiring
US readers: use "120 V AC" on the inverter label. Australian readers: battery systems covered by AS/NZS 5139 have their own mandatory signs. Use those in place of, or as well as, these.
20. Frequently asked questions
Do I really need a fuse if my battery has a BMS?
Yes. A BMS protects the battery's cells, and many can't safely interrupt a dead short. The fuse protects the cables. Use both.
Can I connect a solar panel straight to the battery?
No. Without a charge controller the battery will be overcharged, and a lithium battery's BMS would have to cut off repeatedly. Always use a controller.
Can I use a 37 V house solar panel on a 12 V battery?
Yes, with an MPPT controller rated at 100 V input (such as a 100/30). A cheap PWM controller would waste more than half the power. See Option B.
What size fuse do I need for a 600 W inverter?
At 12 V it draws about 56 A at full power, so use an 80 A fuse at the battery or busbar end, with 16 mm² cable. Always check the inverter manual's recommendation.
How far can the fuse be from the battery?
As close as practical, and no more than about 150 mm (6 in) in this guide. The US RV low-voltage standard (ANSI/RVIA LV) allows up to 18 in (457 mm) from the source; the marine standard ABYC E-11 uses 7 in. The cable between the battery and the fuse is unprotected.
Can I run a fridge from a 600 W inverter?
Usually yes, if it's a pure sine inverter with a good surge rating. A fridge compressor can draw 3–8 times its running power for a moment. Test it before relying on it.
Can I plug the inverter into my house wiring?
No. Back-feeding a building through a socket ("suicide lead") can kill you or a utility worker, and it's illegal. Connecting an inverter to building circuits needs a qualified electrician and proper changeover equipment.
Why does my crimp need a special tool?
Because a poor crimp has extra resistance and heats up under load without blowing a fuse. That's a common cause of DIY solar fires. A hydraulic crimper with the correct die makes a cold-welded joint that stays cool.
How much will it produce in winter?
In London, a 200 W panel averages about 0.27 kWh a day in December, against about 0.75 kWh in June. In Glasgow it's less; in Sydney or Arizona much more. See the sun data section for every month.
21. Shopping list
| Item | Qty | Specification |
|---|---|---|
| Solar panel | 1 | 200 W "12 V" (Voc about 24 V), or Option B: about 410 W household panel (Voc about 37 V). With mounting brackets. |
| MPPT charge controller | 1 | 100 V / 20 A (Option B: 100 V / 30 A, e.g. Victron SmartSolar 100/30) |
| LiFePO4 battery | 1 | 12.8 V 100 Ah, BMS ≥ 100 A, low-temperature charge protection |
| Inverter | 1 | 12 V 600 W pure sine, ideally with RCD/GFCI outlets |
| Fuses and holders | 1 set | MRBF 100 A + terminal fuse block (or Class T 100 A + holder). MIDI/MEGA 80 A, 25 A (Option B: 40 A) and 30 A with holders. |
| Battery isolator switch | 1 | ≥ 100 A continuous, DC rated |
| PV isolator | 1 | 2-pole DC switch or breaker, ≥ 100 V DC (matching the controller), ≥ 16 A (Option B: ≥ 20 A) |
| Busbars | 2 | Positive (or fused distribution block) and negative, with M8 studs |
| Cable | – | 25 mm² and 16 mm² (red and black), 6 mm² (red and black), 6 mm² solar cable with MC4 extension leads |
| Terminals | – | Tinned tube lugs to suit each cable and stud, bootlace ferrules, adhesive heat-shrink in red and black |
| Tools | – | Hydraulic lug crimper (or have the big cables made up), ratchet crimper, ferrule crimper, MC4 crimp tool, cable cutters, torque wrench, multimeter |
| Optional | – | Battery monitor shunt, 12 V blade fuse box, plug-in RCD, smoke alarm, fire extinguisher |
22. Check your own numbers
- Fuse size calculator and DC cable size calculator
- DC voltage drop calculator and AWG to mm² converter
- Inverter battery current calculator and inverter size calculator
- Solar charge controller calculator and solar panel output calculator
- Battery run time calculator and off-grid solar system calculator
- For a detailed crimping guide, see the crimping section of our campervan wiring guide
23. Sources
- European Commission JRC – PVGIS 5.3 (monthly PV and off-grid simulations)
- Samlex – Pure sine wave versus modified sine wave inverters
- Edecoa – Modified vs pure sine wave: effects on inductive loads
- Sterling Power – Inverters DC–AC
- Victron SmartSolar MPPT 100/30 specifications (100 V, 35 A Isc, 440 W at 12 V)
- Example UK 405 W 108-cell panel (Voc 37.23 V)
- Victron – Wiring Unlimited: DC wiring, cables, fuses and connections
- Blue Sea Systems – MRBF terminal fuse (10,000 A interrupt rating at 14 V)
- Littelfuse – MAXI fuse datasheet (1,000 A interrupt rating)
- Blue Sea Systems – DC main overcurrent protection (ABYC fuse placement)
- SolarQuotes – What electrical work you can legally do yourself in Australia
- ANSI/RVIA LV – low-voltage systems standard (fuse location, splice pull tests)
This guide covers a small plug-in system. It isn't a design for wiring into a building's mains installation; that work needs a qualified electrician. OffGridVolts accepts no liability for systems built from it. Always follow the manuals for the parts you buy.
New to some of the terms? See the glossary. Not sure where to start? Try start here.