The formula
The coefficient is negative, and Tmin is below 25 °C, so the result is higher than the label Voc.
Worked example
Three 100 W panels with Voc 22.5 V and a coefficient of −0.29 %/°C, at −10 °C: 22.5 × (1 + −0.0029 × −35) = 24.8 V per panel, or 74.4 V for the string. That's safely inside a 100 V controller. Five of the same panels would reach 124 V and could destroy it.
The low-voltage side
Every MPPT controller has a minimum PV voltage to start charging, and panels lose voltage when hot. The start voltage depends on the model: Victron's SmartSolar and BlueSolar MPPT charge controllers (such as the 75/15 to 250/100) need the PV voltage to exceed battery voltage + 5 V to start, and battery voltage + 1 V to keep running, while Victron's SmartSolar MPPT RS needs 120 V on the PV input to start. Check your controller's manual for its start voltage and keep the string's hot-weather Vmp comfortably above it. The warning in this calculator uses the battery + 5 V rule.
Tips
- Use the coldest temperature you could realistically see at dawn, not the average winter temperature.
- Series wiring lowers current and cable size, but one shaded panel drags down the whole string. See series vs parallel.
Frequently asked questions
How many solar panels in series on a 100V MPPT?
With typical 12 V-style panels (Voc around 22 V), three in series is safe in most UK and US climates. With 60-cell panels (Voc around 40 V) only two.
What happens if Voc exceeds the controller rating?
The controller can be permanently damaged, and it's not usually covered by warranty. Always check with the coldest expected temperature.