The formulas
Examples
- A 1,000 W load at 12 V DC draws 83.3 A, but only 4.3 A at 230 V and 8.3 A at 120 V.
- A 60 W 12 V fridge draws 5 A when running.
- A 2,000 W motor on 230 V with a power factor of 0.8 draws 10.9 A.
The big difference between 12 V and mains current is why 12 V wiring needs much thicker cable for the same power.
Watts to amps chart
Current for resistive loads (power factor 1) such as heaters, kettles and lights. For motors, divide by the power factor (about 0.8), so add 25%. 12, 24 and 48 V columns are DC; take inverter losses into account (add about 12%) when the power comes from a battery through an inverter.
| Watts | 12 V | 24 V | 48 V | 120 V | 230 V | 240 V |
|---|---|---|---|---|---|---|
| 10 W | 0.83 A | 0.42 A | 0.21 A | 0.08 A | 0.04 A | 0.04 A |
| 20 W | 1.67 A | 0.83 A | 0.42 A | 0.17 A | 0.09 A | 0.08 A |
| 50 W | 4.17 A | 2.08 A | 1.04 A | 0.42 A | 0.22 A | 0.21 A |
| 60 W | 5.00 A | 2.50 A | 1.25 A | 0.50 A | 0.26 A | 0.25 A |
| 100 W | 8.33 A | 4.17 A | 2.08 A | 0.83 A | 0.43 A | 0.42 A |
| 150 W | 12.5 A | 6.25 A | 3.12 A | 1.25 A | 0.65 A | 0.62 A |
| 200 W | 16.7 A | 8.33 A | 4.17 A | 1.67 A | 0.87 A | 0.83 A |
| 250 W | 20.8 A | 10.4 A | 5.21 A | 2.08 A | 1.09 A | 1.04 A |
| 300 W | 25.0 A | 12.5 A | 6.25 A | 2.50 A | 1.30 A | 1.25 A |
| 400 W | 33.3 A | 16.7 A | 8.33 A | 3.33 A | 1.74 A | 1.67 A |
| 500 W | 41.7 A | 20.8 A | 10.4 A | 4.17 A | 2.17 A | 2.08 A |
| 600 W | 50.0 A | 25.0 A | 12.5 A | 5.00 A | 2.61 A | 2.50 A |
| 700 W | 58.3 A | 29.2 A | 14.6 A | 5.83 A | 3.04 A | 2.92 A |
| 750 W | 62.5 A | 31.2 A | 15.6 A | 6.25 A | 3.26 A | 3.12 A |
| 800 W | 66.7 A | 33.3 A | 16.7 A | 6.67 A | 3.48 A | 3.33 A |
| 900 W | 75.0 A | 37.5 A | 18.8 A | 7.50 A | 3.91 A | 3.75 A |
| 1,000 W | 83.3 A | 41.7 A | 20.8 A | 8.33 A | 4.35 A | 4.17 A |
| 1,100 W | 91.7 A | 45.8 A | 22.9 A | 9.17 A | 4.78 A | 4.58 A |
| 1,200 W | 100 A | 50.0 A | 25.0 A | 10.0 A | 5.22 A | 5.00 A |
| 1,500 W | 125 A | 62.5 A | 31.2 A | 12.5 A | 6.52 A | 6.25 A |
| 1,800 W | 150 A | 75.0 A | 37.5 A | 15.0 A | 7.83 A | 7.50 A |
| 2,000 W | 167 A | 83.3 A | 41.7 A | 16.7 A | 8.70 A | 8.33 A |
| 2,200 W | 183 A | 91.7 A | 45.8 A | 18.3 A | 9.57 A | 9.17 A |
| 2,400 W | 200 A | 100 A | 50.0 A | 20.0 A | 10.4 A | 10.0 A |
| 2,500 W | 208 A | 104 A | 52.1 A | 20.8 A | 10.9 A | 10.4 A |
| 3,000 W | 250 A | 125 A | 62.5 A | 25.0 A | 13.0 A | 12.5 A |
| 3,200 W | 267 A | 133 A | 66.7 A | 26.7 A | 13.9 A | 13.3 A |
| 3,500 W | 292 A | 146 A | 72.9 A | 29.2 A | 15.2 A | 14.6 A |
| 4,000 W | 333 A | 167 A | 83.3 A | 33.3 A | 17.4 A | 16.7 A |
| 4,500 W | 375 A | 188 A | 93.8 A | 37.5 A | 19.6 A | 18.8 A |
| 5,000 W | 417 A | 208 A | 104 A | 41.7 A | 21.7 A | 20.8 A |
| 6,000 W | 500 A | 250 A | 125 A | 50.0 A | 26.1 A | 25.0 A |
| 7,000 W | 583 A | 292 A | 146 A | 58.3 A | 30.4 A | 29.2 A |
| 7,500 W | 625 A | 312 A | 156 A | 62.5 A | 32.6 A | 31.2 A |
| 8,000 W | 667 A | 333 A | 167 A | 66.7 A | 34.8 A | 33.3 A |
| 8,500 W | 708 A | 354 A | 177 A | 70.8 A | 37.0 A | 35.4 A |
| 9,000 W | 750 A | 375 A | 188 A | 75.0 A | 39.1 A | 37.5 A |
| 10,000 W | 833 A | 417 A | 208 A | 83.3 A | 43.5 A | 41.7 A |
| 12,000 W | 1,000 A | 500 A | 250 A | 100 A | 52.2 A | 50.0 A |
| 15,000 W | 1,250 A | 625 A | 312 A | 125 A | 65.2 A | 62.5 A |
What the numbers mean for plugs and circuits
| Country | Plug or circuit | Maximum continuous power |
|---|---|---|
| UK | 13 A plug at 230 V | About 3,000 W |
| UK | 32 A ring or radial circuit | About 7,360 W in total |
| USA | 15 A circuit at 120 V | 1,800 W; 1,440 W for continuous loads (80% rule) |
| USA | 20 A circuit at 120 V | 2,400 W; 1,920 W continuous |
| USA | 30 A RV hookup at 120 V | 3,600 W |
| USA | 50 A RV hookup, 120/240 V split-phase | 12,000 W (two 50 A legs) |
| Australia | 10 A plug at 230 V | 2,300 W (2,400 W at 240 V) |
| Australia | 15 A plug (larger earth pin) | About 3,450 W |
Frequently asked questions
How many amps is 1000 watts at 12V?
About 83 A. Through an inverter, add around 12% for losses, so roughly 95 A from the battery.
How many amps is 3000 watts at 230V?
About 13 A, which is the maximum for a UK plug. At 120 V it's 25 A.
How many amps is 1100 watts?
About 4.8 A at 230 V, 9.2 A at 120 V and 92 A at 12 V DC.
How many amps is 2000 watts at 120V?
About 16.7 A, more than a 15 A US circuit can supply continuously. It needs a 20 A circuit.
How many amps is 3200 watts?
About 13.9 A at 230 V, 26.7 A at 120 V, or 267 A at 12 V DC.
How many amps is 8500 watts?
About 37 A at 230 V, 35 A at 240 V and 71 A at 120 V. A load that size needs its own dedicated circuit.